ENGLISH - 2/8

Power supply must be in the range 19 to 40 Vdc (at any polarity), or 19 
to 28 Vac – also consult the section Installation standards.
The upper limits must not be exceeded, otherwise the module may be 
seriously damaged.
The power source must be protected against any trouble to the module 
by a fuse of adequate size.

ELECTRICAL CONNECTIONS

INPUTS (Max frequency  400 Hz)

OUTPUT

REGULATION OF PULSE DURATION

2 3

19-40Vcc
19-28Vca

POWER SUPPLY

19-40Vdc

19-28Vac

8

Contact / Reed

NAMUR

NPN (2 wires)

Photo electric

NPN 24V (3 wires)

PNP 24V (3 wires)

NPN 12V (3 wires)

7

8

7

9

9

7

9

8

9

8

10

9

10

11

10

10

12

+

-

+

s

-

+

s

-

-

+

s

+

-

4 5 6

Relay with 1 SPDT changeover with capacity 5 A 250 Vac
(resistive load)

Via the trimmer on the front panel it is possible to regulate the duration of the pulse 
from a minimum of 100 msec to a maximum of 500 msec.
To reduce the pulse duration, rotate the trimmer anticlockwise (- sign) and to increase, 
rotate the trimmer clockwise (+ sign).