background image

ENGLISH - 1/8

MI000224-E

Z112A

Amplifier with pulse divider for ON-OFF sensors

EN

Pulse input for all the most common sensors: mechanical contact, 
reed, 2 and 3 wire npn with 12Vdc and 24Vdc power supply, 3 wire 
pnp with 24Vdc power supply, NAMUR, photoelectric.
Max frequency  400 Hz.
Divider circuit programmable by  dip switch from 1 to 256.
Adjustment of pulse duration at output from 100 msec to 500 msec by 
means of trimmer on front panel.
Relay output with 1 SPDT changeover with capacity 5 A 250 Vac  
(resistive load).
Front panel LED indication of power on and relay energised.
Insulation between power supply and inputs: 1500Vac, insulation to 
output > 3000Vac.

GENERAL CHARACTERISTICS

TECHNICAL SPECIFICATIONS

19 – 40 Vdc, 19-28 Vac 50-60Hz, max 2.5W.

Pulses: mechanical contact, reed, 2 and 3 wire npn with 
12Vdc and 24Vdc power supply, 3 wire pnp with 24Vdc 
power supply, NAMUR, photoelectric.
Max frequency  400 Hz.

Relay with 1 SPDT changeover with capacity 5 A 250 Vac  
(resistive load).

Temperature: 0..50°C, Humidity -  min:30%, max 90% at 
40°C non condensing (also see section Installation 
standards).

EN61000-6-4 (electromagnetic emissions, industrial ambient)
EN61000-6-2 (electromagnetic immunity,  industrial ambient)
EN61010-1 (safety)

Power supply:

Inputs:

Outputs:

Ambient conditions:

The instrument 
conforms to the 
following standards:

Reviews: