![Seneca Z109TC2-1 Installation Manual Download Page 8](http://html1.mh-extra.com/html/seneca/z109tc2-1/z109tc2-1_installation-manual_1239539008.webp)
ENGLISH - 8/8
OUTPUT SELECTION
DIP-switches 7 and 8 of the SW2 group can be used to set the output with or without zero elevation, and
the normal or inverted output respectively. DIP-switch SW3 can be used to select the output type.
Note: the
DIP-switches must be set with the power supply disconnected from the module, to avoid
electrostatic discharges and damage to the module.
LED SIGNALS ON THE FRONT PANEL
LED
Status
LED meaning
PWR/FAIL
Green
On
The device is powered correctly
Flashing (1 flash/sec.)
Out of scale, Burn Out or internal fault
Flashing (
"'
2 flashes/sec.)
DIP-switch setup error
ACCESSORIES
Code
Description
CU-A-MICROB
USM - microUSB 1 metre communication cable
CU-A-MICRO-OTG
Mobile phone adapter cable
CONTACT INFORMATION
Technical support
Product information
t
SW2: OUTPUT MODE AND SCALE
POSITION
OUTPUT
POSITION
OUTPUT
7
RANGE
8
MODE
0..20mA / 0..10V
NORMAL
4..20mA / 2..10V
REVERSE
SW3: OUTPUT TYPE
POSITION
OUTPUT
POSITION
OUTPUT
1 2
TYPE
1 2
TYPE
VOLTAGE
CURRENT
KEY
ON
OFF