ELECTRICAL CONNECTIONS

For signals connection please use shielded cables; the equipment cable 
shields must be connected to a preferential ground. It’s also a good rool 
avoid to pass wires near power installation cables like transformers, 
inverters, motors, induction ovens etc.

HOW TO INSTALL

Z109S module is designed to be 

 on a DIN 46277 bar, in 

installed

vertical position.
For working properly and long life, make sure that adequate ventilation is 
provided for the module, avoiding placing raceways or other objects which 
could obstruct the abat-vents. Avoid to install module over equipment that 
generates heat.
We suggest you to install the module in the lower part of the cabinet.

HEAVY WORKING CONDITIONS:

Heavy working conditions are:

     High power voltage a (> 30V    / > 26 V   ).
     Input sensor feeded.
     Use of output in impressed current.

When modules are installed side by side it may 

be necessary

 

to 

separate them at least 5 mm

 in the following cases:

     Upper board temperature higher than 45°C and at least one of the
     heavy working conditions verified.
     Upper board temperature higher than 35°C and at least two of the
     heavy working temperature verified.

OUTPUT

mA

4 5 6

I

mA

4 5 6

I

ACTIVE  OUTPUT

  :  use  this  connection  when  output  loop  is  to  be 

directly feeded from Z109S module.
Loop power supply given by Z109S module is protected against short 
circuit.
Max load resistance 600 ohm.

PASSIVE OUTPUT

 : use this connection if current loop's power supply 

is given from external.