USB CONNECTION (R-32DIDO MODEL ONLY)
The front USB port allows a simple connection using the Modbus RTU slave protocol, the communication
parameters for the USB port cannot be modified:
Baud rate: 115200
Address of the Modbus RTU station: 1
Data Bit: 8
Stop bit: 1
Drivers for Windows PC can be downloaded from the device's web page.
The drivers are anyway present in the installation of the "Easy Setup 2" software.
RESETTING THE DEVICE TO FACTORY CONFIGURATION
It is possible to reset the device to the factory configuration using the following procedure:
1)
Remove the device back cover
2)
With the device off, set dip switch SW3 dip 1 and 2 to ON
3)
Power up the device and wait 10 seconds
4)
Turn off the device
5)
With the device off, set dip switch SW3 dip 1 and 2 to OFF
6)
Power up the device
7)