ERT-10-2-221C
ERT-10-2-222C

1,5 HP

Programming
key

230Vac

Thermostat
probe

Thermostat
probe

Defrost
probe

Defrost
probe

N

L

ERT-10-2-221C

ERT-10-2-222C

Connections - output

5. LED display (3 - digit )

SdL

- In standard mode it displays detector temperature determined by the

parameter

(0 – thermostat probe, 1 – defrost probe). Displayed temperature range: between - 40 C and + 40 C.
Temperature below -10 C is displayed with resolution of 1 C, and temperature above -9.9 C with resolution of
0.1 C. In change settings mode (SET button highlighted) the set temperature is displayed. In programming mode –
parameter editing - parameter symbol or value is displayed. Alarm codes and service code being input are also
displayed (in service code input verification).

O

O

O

O

O

O

ALARM

ALARM

AUX

AUX

According to the parameter

‘rL3’

According to the parameter

‘rL2’

10A

5A

5A

Programming
key

2

3

4

5

6

7

9 8

1

230Vac

N

L

AUX

AUX

ERT-10-3-321C

Dimensions and mounting

Mounting hole

71x29 mm

Regulator panel 77,2x36 mm

Housing dimensions behind mounting panel
with side catches and disassembled
cramps

Width - 83,5 mm
Height - 37 mm
Depth - 80 mm

2

Programming temperature setting

SET

UP

DOWN

SET

SET

SET

Manual defrosting

dEt

DOWN/DEF

DOWN/DEF

Access to configuration parameters commonly available without a service code

PRG

Access to all configuration parameters

PRG

SET

UP

DOWN

PRG

SET

Parameter modification

UP

DOWN

SET
UP

DOWN

SET

Saving new parameter values

PRG

To display or modify settings:
1) Press and hold

for more than 1 second. The temperature setting is displayed and the button is highlighted.

2) Set the temperature using

and

.

3) Confirm by pressing

again. Highlighting

button is off. Current temperature is displayed.

If

button is not pressed for 30 seconds, previous settings are restored.

It is possible to initiate defrosting manually. The necessary condition is that defrost probe temperature is below
(

(final defrosting temperature) -1

). To initiate defrosting process press and hold

for more than 5

seconds. Manual process initiation is signaled by flashing

button. When theprocess is initiated automatically

the button is highlighted continuously.

Press and hold

for more than 5 seconds, the screen displays the code of the first commonly available parameter.

1) Press and hold

and

for more than 5 seconds, the screen displays “0”.

2) Press

or

to display “33” (password granting access to all configuration parameters).

button

returns to normal running mode.
3)

confirms the password. Confirming incorrect password displays “0”.

4) Correct password – code of the first modified parameter is displayed.

After displaying code of the first parameter:
1) Press

or

to display the number of a parameter to modify.

2) Press

to display parameter value.

3) Press

or

to increase or decrease parameter value.

4) Press

to initially save new parameter value and return to parameter code display.

5) To modify other parameters, repeat steps 1 to 4.

To save modified values, press and hold

for more than 1 second and the programming procedure is

terminated.

O

C

Summary of Contents for ERT-10-3-321C

Page 1: ...symbol or increases the value In input service code mode pressing the button increases the code number button holding for more than 5 seconds activates manual defrosting signaled by flashing Automatic defrosting is signaled by continuous highlighting In change setting mode button highlighted pressing the button decreases the temperature In parameter modification mode pressing the button displays p...

Page 2: ...ET UP DOWN SET Saving new parameter values PRG To display or modify settings 1 Press and hold for more than 1 second The temperature setting is displayed and the button is highlighted 2 Set the temperature using and 3 Confirm by pressing again Highlighting button is off Current temperature is displayed If button is not pressed for 30 seconds previous settings are restored It is possible to initiat...

Page 3: ...limits min compressor standstill time and max compressor running time Unit special running modes COMP CFn COMP CFn COMP Special functions PRG Std DOWN Alarms Std EE E0 E1 HI L0 To enter special mode press and hold for more than 5 seconds Compressor always off mode 1 is signaled by short flashes of button Compressor always on modes 2 or 3 signaled by longer flashes of button 1 Holding while initiat...

Page 4: ...transmitter on during HI message 4 alarm LO transmitter on during LO message 5 LO and HI alarms transmitter on during LO and HI messages 6 defrosting only ERT 10 2 221C and ERT 10 2 222C Relay output 3 function 0 inactive off 1 fan 2 lighting PRG button 3 alarm HI transmitter on during HI message 4 alarm LO transmitter on during LO message 5 LO and HI alarms transmitter on during LO and HI message...

Reviews: