Zone heating / cooling controller

ZCE6 Basic and ZCE6 Advance

EN

Instructions for use and setup

Summary of Contents for ZCE6 Basic

Page 1: ...Zone heating cooling controller ZCE6 Basic and ZCE6 Advance EN Instructions for use and setup...

Page 2: ...ix independent temperature zones with the possibility of controlling fourteen heating cooling units in total The ZCE6 Advance controllers also enable the control of the energy source mixing valve and...

Page 3: ...control of thermal actuators 7 Connection terminals for connecting wired room units 8 Connection terminals for connecting temperature sensors and digital inputs 9 Connection terminals for the BUS conn...

Page 4: ...operation When the LED light is on the mixing valve opens when the LED light is on the mixing valve closes Signalization of the leading Master controller in BUS con nection When the LED light is on t...

Page 5: ...ish 5 MENU In the menu we carry out basic settings of the controller We move from the home screen to the menu by holding the key for 2 seconds we move between individual groups in menu by pressing the...

Page 6: ...HYDRAULIC SCHEME The ZCE6 Advance controller has three hydraulic schemes to choose from the ZCE6 Basic only 1 scheme Hydraulic schemes are shown in chapter Hydraulic schemes Example Shift from scheme...

Page 7: ...nglish 7 MENU PAIRING OF ROOM UNITS With the pairing process we connect the RCD room unit with the controller and at the same time assign zones to it Example Pairing the RCD room unit with zone 1 and...

Page 8: ...8 English MENU MASTER CONTROLLER If more controllers are connected to the BUS connection one controller must be set as the leading Master controller Example Setting the master controller...

Page 9: ...PAIRING OF THE CONTROLLERS MASTER CONTROLLER When more controllers are interconnected in the BUS connection the controllers must be connected paired Example Activation of the pairing process on the ma...

Page 10: ...NG OF CONTROLLERS SLAVE CONTROLLER After activating the pairing process on the master controller pairing on slave con trollers must also be activated Example Activation of the pairing process on the f...

Page 11: ...ish 11 MENU MANUAL MODE During start up or testing of the controller the zone outputs circulation pumps source or mixing valve can be manually switched on or off Example Manual ON OFF of the zone 3 ou...

Page 12: ...RESET There are three types of resets available RESET 1 pairing reset of room units RESET 2 pairing reset of controllers RESET 3 reset of the entire controller to the factory settings Example Activat...

Page 13: ...MP 3 FROST PROTECTION TEMP 4 TEMP DEFINED WITH PARAMETER C1 5 0 C1 5 REQUESTED TEMPERATURE OF DIGITAL INPUT EX TERNAL TIMER This setting defines what kind of temperature shall be maintained in case of...

Page 14: ...ol algorithm for temperature zones When set to 0 the setting of the control algorithm on each individual room unit is taken into account while by the 1 2 and 3 settings the control algorithm for all t...

Page 15: ...influence 0 1 3 0 1 0 C4 4 SUPPLY LINE TEM PERATURE This setting determines how the supply line temperature is determined 1 WEATH ER COMPEN SATED 2 CONSTANT TEMP 1 C4 5 CONSTANT SUPPLY LINE TEMPERATUR...

Page 16: ...open position 7 30sec 15 C4 20 INITIAL MIXING VALVE MOVEMENT FROM CLOSED POSITION Setting of initial mixing valve movement duration when moving from closed position 7 30sec 15 BACKUP OPERATION PARAMET...

Page 17: ...ROOM UNIT ON ZONE 2 Setting of influence of room unit on the heating zone 2 0 ROOM UNIT 1 1 ROOM UNIT 2 2 ROOM UNIT 3 3 ROOM UNIT 4 4 ROOM UNIT 5 5 ROOM UNIT 6 6 NO INFLU ENCE 6 C8 3 INFLUENCE OF ROOM...

Page 18: ...om unit to be connected to wire input 2 0 ROOM UNIT 1 1 ROOM UNIT 2 2 ROOM UNIT 3 3 ROOM UNIT 4 4 ROOM UNIT 5 5 ROOM UNIT 6 6 NO INFLU ENCE 6 C8 9 ROOM UNIT ON WIRE INPUT 3 Setting of room unit to be...

Page 19: ...000000 1 000001 2 000010 3 000011 0 C8 15 RF CHANNEL Setting of the RF frequency channel through which the controller communicates with wireless room units 0 7 0 C8 16 CONTROLLER RF ADDRESS Setting of...

Page 20: ...ature from required room temperature within the ED time constant period The length of the ED period is set on the room unit for each heating zone separately With parameter C2 3 the width of the zone i...

Page 21: ...der operating voltage C3 4 2 inverted operation when the circulation pump is on there is no operating voltage at the output Energy source and circulation pump ZCE6 Advance Up to 6 RCD room units can b...

Page 22: ...external timer The mixing valve is controlled by closing and opening impulses P constant in time periods I constant When in heating mode the measured temperature of supply line is below the desired t...

Page 23: ...over of operation from cooling to heating When a short circuit is detected on the digital input cooling the control ler switches over to the cooling mode For the operation of digital input cooling the...

Page 24: ...which is connected to the input dew point C1 7 0 input is not used C1 7 1 digital sensor of type NC short circuit when dew point is detected C1 7 2 digital sensor of type NO open connection terminals...

Page 25: ...ration mode C1 15 1 the voltage of 10V for sensor power supply is always available at the output C1 15 2 the 0 10V output signal is used to operate the source Output 10V Dependency graph of output vol...

Page 26: ...et with parameter C7 2 The operating time percentage of period of a certain zone is set with parameters C7 3 for zone 1 to C7 8 for zone 6 Backup operation All control outputs that haven t been activa...

Page 27: ...English 27 CONTROLLER INSTALLATION 1 2 3 4...

Page 28: ...ropriate qualifications or by an authorised organisation Before interfering with the wiring make sure the main switch is switched off Follow the regulations for low voltage installations IEC 60364 and...

Page 29: ...ontrol with a voltage of 24V the protective cover has to be removed the switch has to be put in the position of 24V and a special purpose transformer with a voltage of 24V has to be connected to the c...

Page 30: ...30 English Hydraulic scheme 1 230V ZCE6 Basic and Advance HYDRAULIC SCHEMES...

Page 31: ...English 31 Hydraulic scheme 1 24V ZCE6 Basic and Advance...

Page 32: ...32 English Hydraulic scheme 2 230V ZCE6 Advance...

Page 33: ...English 33 Hydraulic scheme 2 24V ZCE6 Advance...

Page 34: ...34 English Hydraulic scheme 3 230V ZCE6 Advance...

Page 35: ...English 35 Hydraulic scheme 3 24V ZCE6 Advance...

Page 36: ...ER Using the enclosed cable the controllers have to be paired see chapter MENU PAIRING OF CONTROLLERS With the pairing process the communication connections between controllers and the order of the co...

Page 37: ...flashes Error in connection with slave controllers What can I do Check the cable connection to BUS connection on master and slave controllers If the error is not resolved the controllers must be serv...

Page 38: ...y consumption 2100W Energy consumption in the standby mode 0 5W Degree of protection IP 20 acc to EN 60529 Safety class I according to EN 60730 1 Housing PC ABS thermoplastic Dimensions w h d 233 163...

Page 39: ...llection point for waste electrical and electronic equipment WEEE Suitable disposal of this product prevents nega tive impact on the environment and health which could otherwise be caused by improper...

Page 40: ...serve the right to errors changes and improvement without prior notice SELTRON d o o Tr a ka cesta 85 A SI 2000 Maribor Slovenija tel 386 0 2 671 96 00 fax 386 0 2 671 96 66 http www seltron si email...