WM1200 ELECTRICAL SPECIFICATIONS
INVERTER TYPE
PWM Full Bridge power stage, with true sine wave AC output.
SELECTRONIC WM1200 INVERTER SPECIFICATIONS
ELECTRICAL
PARAMETER
WM1200
CONDITION
Output Power
@ 25 °C Ambient
1,400 watts
1,800 watts
3,600 watts
Max Continuous
1/2 Hour Rating
Max Surge
Output Power
@ 40 °C Ambient
1,200 watts
1,600 watts
3,600 watts
Max Continuous
1/2 Hour Rating
Max Surge
Voltage Input Range
10 - 17V DC
Range
Input Current
0.05A DC
0.7A DC
136A DC
349A DC
Stand By
Inverter ON – No Load
Max Continuous 25
°
C
Max Surge 25
°
C
Demand Start Sensitivity
Response Time
Factory Setting
4-16W
1 Second Max
4W
User Adjustable
Factory Setting
Low Voltage Shutdown
High Voltage Shutdown
Factory Setting
(Low Voltage Shutdown)
10 – 11.5V DC
17V DC
11.0V DC
User Adjustable
Fixed
Factory Setting
Output Voltage
240V AC +/- 4%
@ Nominal DC Input,
No Load to Full Load
Output Current
5.8A AC
15A AC
Max Continuous
Max Surge
Output Wave Shape
Output Frequency
Total Harmonic Distortion
Efficiency
True Sine Wave
50Hz +/- 0.01%
< 4%
Peak 91% Full load 85%
Power Factor Limitations
Nil
Input / Output Isolation
1,875VAC
Memory Retention
Permanent
Operating Temperature Range -10 °C to 50 °C
Conforms to standards
AS 3100 (wiring), AS 3108, C tick
MECHANICAL
Size
410mm wide x 175mm high x 342mm deep
Weight 14kg
Weight Packed
17kg
Input Lead Length
1.5 metres
Output Wiring Method
Three terminal junction box with conduit knock outs
Chassis
Powder coated zinc steel (Wedgwood Blue)
DC Isolation
Single Pole Circuit Breaker ( Non auto )
Warranty
5 year parts and labour (Conditions apply)
Notes:
The above specifications are based on unity power factor.
The DC Input is electrically isolated from the AC Output.
Through a policy of continued development, specifications are subject to change without notice