OPERATING  INSTRUCTIONS

                                                  

(Specifications subject to change as development is a continuous process)

selectron 

Process Controls Pvt. Ltd., 

TEL:  28471882, 28476443  FAX : 2847 1733   E-mail - [email protected]   Website: www.selecindia.com

Document name: Operating / 0410/XT242/standard/ version4     OP007-V4(page 1 of 2)

SPECIFICATIONS :

DISPLAY                   

Current value: 4 digit red. 

Set value: 4 digit green, both 0.5" height.

SET POINTS

 2.

TIME RANGES

99.99 / 999.9 / 9999 sec, 99:59 min:sec,          
999.9 / 9999 min, 999.9 / 9999 hr.

COUNTING 
DIRECTION

Up / Down.

BATCH 
COUNTS

Up to 9999.

MODES

a) ON delay b) Interval c) Cyclic ON first 
d)Cyclic OFF first.

TIME SETTING

By front keypad.

MEMORY

10 years.

LED INDICATION

a) Relay status b) Time unit (sec / min / hr) 
Note: When timing is in progress unit LED 
blinks to indicate timing on & unit of range. 
When timing is in hold mode, blinking stops.

OUTPUTS  

2 C/O  (DPDT). 

RELAY RATING

5A @ 230 V AC/ 28 V DC resistive load.

INPUTS

a) Start b) Reset

CONFIGURATION

via rear terminals.

LOCK
RESET

a) Front panel.
b) Rear terminal.
c) ON power interruption (programmable).

RESET TIME 

Less than 100 msec.

ACCURACY

± 0.05% or 50 msec whichever is greater.

SUPPLY

90 to 270V AC/DC @ 50/60Hz. 

MOUNTING

Panel mounting.

HOUSING

ABS.

WEIGHT

375 gms. (approx).

o

TEMPERATURE

Operating: 0 to  50 C. 

o

Storage: -5 to 55  C.

HUMIDITY

95% RH.

3  

RESET

4  

COM for Start / Reset

5  

START  

7  

NO of relay 1

8  

COM of relay 1

9  

NC of relay 1

10  

NO of relay 2

11  

COM of relay 2

12  

NC of relay 2

13 & 14 

Configuration lock 

15  

LIVE (SUPPLY)  

16  

NEUTRAL (SUPPLY)

TERMINAL CONNECTIONS

L

N

RELAY1

RELAY2

COM

COM

NC

NC

NO

NO

 1    2    3    4    5    6   

 13 
 14 

 15 
 16 

7     8   9    10  11  12

RST

STRT

COM

C

O

N

F

IG

U

R

A

T

IO

N

 

L

O

C

K

Reset  Start

ELECTRICAL PRECAUTIONS DURING USE

eparate shielded wires for inputs.

High voltage spikes are generated in industrial electrical systems due to the 
switching / operation of inductive loads, termed as 'Noise'. Noise can create 
momentary disruption, erratic display, latch up, data loss or permanent dam-
age to the instrument. To reduce noise:
a) Use of MOV across supply of timer & snubber circuits across loads are re-
commended
b) Use s

Front view 

72

72

Side view

68

115

Panel cutout

69

69

10

RESETTING THE XT242
A) By front key : (programmable) 

2. By 

B) Remote reset : 

The XT242 can be reset from a remote 

push button as shown in the figure.

1. By pressing ENT key continuously for 3 sec. 

pressing ENT key momentary

 1          2      3       4       5        6   

RST

COM

Reset switch

OPERATING MODES :

t

Supply voltage

Start Contact

NO Contact

t =  Set delay time

  

Function : On delay-pulse
                    start

tt

Supply Voltage

Reset Contact

NO Contact

t = Delay time

  

Function :  Reset

t

1

t

2

Supply 
Voltage

NO

Contact

t =  On time, t  = off time

1

2

Function : Cyclic 
                    (On  time  first)

t

2

t

1

Supply 
Voltage

NO

Contact

t =  On time, t  = off time

1

2

Function : Cyclic 
                    (Off  time  first)

t

Supply 
Voltage

NO

Contact

t

=  Set delay time

  

Function :  On delay

t

Supply 
Voltage

NO

Contact

t

=  Set delay time

  

Function :  Interval delay

t

2

t

1

Supply voltage

Gate Contact

NO Contact

t=delay time = t +t , t  = hold time

1

2

h

Function:  Gate start-On delay

t

h

Supply voltage

NO Contact

S = Start up time

 

t1 = On time, t2 = Off time

Function : Cyclic (ON time  first) 
at S1 & S2 start up time given

                   

Supply voltage

NO Contact

S = Start up time

 

t1 = On time, t2 = Off time

Function : Cyclic (OFF time  first) 
at S1 & S2 start time given

                   

t1

t1

S

t2

t2

t2

t2

S

t1

t1

NOTE

: Use snubber across inductive load to increase life of the internal 

relay of the timer.     

TYPICAL CONNECTIONS FOR LOADS :

1) 

N

L

C      NO

T

LOAD

R            C

T

Snubber

T

T

C      NO

N

L

Contactor

LOAD

C

Snubber

R            C

2) 

selec

XT242     

DUAL SET POINT PROGRAMMABLE TIMER

TERMINAL

DESCRIPTION