Selec PIC152N Operating Instructions Download Page 3

Doc name : OP INST PIC152N

OP168 V04 (Page 3 of 4)

KEY PRESS

DISPLAY

DESCRIPTION

Press     key to select Alarm mode.

Default setting :

In

default setting is

level 2

Alarm mode *

Alarm off

High Alarm

Low Alarm

Band Alarm

Fault Diagnosis Alarm

Fail Output Alarm

Display

Display

Display

Display

Display

for 1sec

for 1 sec.

for 1 sec.

for 1 sec.

for 1 sec.

Press

+

Press

+

Press

+

Press

+

Press

+

Press

+

Press

+

Press

+

Press

+

Press

+

Used to avoid alarm at
power ON. Alarm is
enabled only after the
process value has
reached the set point.

Hold Alarm*

Press     key to select Alarm latch status.

NOTE : This parameter is not prompted when alarm mode is

When latch is ON Alarm
status will be preserved
at any process condition.

Default setting :

Latch alarm*

Press     key to select Alarm hold status.

NOTE : This parameter is not prompted if alarm mode is

Default setting :

Default setting :

Alarm annunciator*

LED of alarm1 blinks
at the rate of 0.2sec

LED blinking ;
display flashing b/w
PV and message

at 1 sec.

(ALRM)

No annunciator

Press     key to select Relay status for alarm1.

Relay status for Alarm1

Relay Energized.

Relay De - energized

NOTE : This parameter is not prompted when alarm mode is

Press     key to select Alarm annunciator.

NOTE : This parameter is not prompted if alarm mode is

Default setting :

PROGRAMMING OF LEVEL 3

NOTE :

Applicable only if Analog output is available.

KEY PRESS

DISPLAY

DESCRIPTION

Press      +      till Level 3 is displayed

Default setting :

Display

Display

Display

Display

Display

for 1sec

for 1sec

for 1 sec.

for 1 sec.

for 1 sec.

Used to set manual
output On / Off.

Press      key to select Manual.

Manual

Parameters in this level
can be set.

Press

+

Fixed 1 C resolution for
TC / RTD.

o

For AIN display as per decimal
point selected.

Programmable from
-1999 to 9999.

Press      key to select Analog high scaling point

Press      key to select Analog low scaling point

Low scaling point

NOTE : This parameter is prompted only if manual is

Default value : 9999

Default value : -9999

Programmable from
-1999 to 9999

High scaling point

Press

+

/

to change value

NOTE : This parameter is prompted only if manual is

Press

+

/

to change value

Press

+

/

to change value

Fixed 1 C resolution for
TC / RTD.

o

For AIN display as per decimal
point selected.

Default setting :

Incase of sensor failure
the output can be set to
high or low value of
range.

Sensor error level

Default setting :

NOTE : This parameter is prompted only if manual is

Programmable from
0.0 to 100.0

Press     key to select Analog output %.

Analog output %

Press     key to select Sensor error level

Press

+

KEY PRESS

DISPLAY

DESCRIPTION

Eg. For 4-20 mA if constant 12mA output current is desired
then setting for manual output :

(Selection for manual

output mode)

display momentarily

Adjust the display to
50.0 to get 12mA at
output

Press

+

/

Press

+

/

Press

Press

+

Press

SETTING FOR RETRANSMISSION MODE

and then display

(Selection for

retransmission mode)

Adjust the display to 0

Select the Input type
as RTD
is displayed

is displayed

display momentarily

Eg. : 1) For Temperature Input :

Input : RTD Input
Retransmission output : 4 - 20 mA
Desired output : 4mA at 0 C, 20mA at 400 C
Settings :

0

0

Press

Press

Press

Press

Press

Using

+

/

Press

+

till

till

Press

+

/

Press

Press

+

+

USER GUIDE

USER GUIDE

ALARM MODES

High Alarm:

Low Alarm:

Band Alarm:

Fault Diagnosis Alarm:

Fail Output Alarm:

Latch Alarm:

Hold Alarm:

The alarm is turned ON when PV rises above a preset
value.

The alarm is turned ON when PV falls below a preset
value.

The alarm is turned ON when PV rises above or falls
below a preset value.

The alarm is turned ON in case a hardware failure
occurs.

The alarm is turned ON in case of :

a) measurement value exceeds  range
b)Sensor reverse condition(applicable for TC/RTD).

This function is used to latch the alarm. When activated,
the alarm is latched until it is acknowledged manually,
even though the alarm condition may have disappeared.

When hold is selected, in any alarm mode, it prevents
an alarm signal on power-up. The alarm is enabled only
if the process temperature is within alarm range.

(1) Press the      key  to view the status of alarms
(2) Press             to view the status of next alarm

(after alarm 2 it rolls over to alarm 1).

Alarm status (e.g : of alarm 1) will be displayed as
follows:
LA-1 for low alarm, HA-1 for high alarm,
FO-1 for Fail output alarm, FD-1 for fault diagnosis.

3) Press             to acknowledge the particular alarm

(Alarm will be acknowledged only if latch ON).

The filter is an adaptive digital filter that discriminates

between measurement noise and actual process
changes. If the signal is varying too greatly due to
measurement noise, increase the filter value. If the fastest
controller response is needed, decrease the filter value.

This value offsets the indicator's PV display value by the
entered amount. This is useful in applications in which the
sensor cannot provide the actual temperature signal due
to mounting constraints, inaccuracy etc.

Alarm display options :

(

Only the alarms that are active can be viewed.

FILTER TIME CONSTANT :

BIAS :

SCALING FOR ANALOG INPUT :

To scale the controller, two scaling points are

necessary. Each scaling point has a coordinate pair of
Display Values and Input Values. It is recommended that
the two scaling points be at the low and high ends of the
input signal being measured. Process value scaling will be
linear between and continue past the entered points to the

ISC.L = 0.00
DSC.L = 0.0
RSCL = no
ISC.H = 20.00
DSC.H = 9999

INPUT

9999

0.0

0.00mA

20.00mA

DISPLAY

SETTING FOR MANUAL OUTPUT MODE :

NOTE :

This change will not be visible in the programming menu.

limits of the input range. (Factory settings example will
display 0.0 at 0mA input and  display 9999 at 20.00mA
input.) Reverse acting indication can be accomplished by
setting reverse scaling parameter as YES. In this case
referring the above eg. For 0.00mA input the display will
show 9999 and 20.00mA input the display will show 0.0.

+

+

Summary of Contents for PIC152N

Page 1: ...e of short wire with adequate ratings and twists of the same in equal size shall be made 5 Cable used for connection to power source must have across section of 1mm or greater These wires shall haveinsulation capacity made of at least 1 5KV 1 The equipment should be cleaned regularly to avoid blockage of ventilating parts 2 Clean the equipment with a clean soft cloth Do not use Isopropyl alcohol o...

Page 2: ...y value scaling point 2 Range DSCL to 9999 For AIN display as per decimal point selected Default value 9999 Display value scaling point high DSCH to change value to change value mark explained in the user guide AIN Analog Input Note KEY PRESS DISPLAY DESCRIPTION Input value scaling point high ISCH Range ISCL to 20 00mA 56mV 10 00V default value changes as per analog input selected Press key to sel...

Page 3: ...ection for retransmission mode Adjust the display to 0 Select the Input type as RTD is displayed is displayed display momentarily Eg 1 For Temperature Input Input RTD Input Retransmission output 4 20 mA Desired output 4mA at 0 C 20mA at 400 C Settings 0 0 Press Press Press Press Press Using Press till till Press Press Press USER GUIDE USER GUIDE ALARM MODES High Alarm Low Alarm Band Alarm Fault Di...

Page 4: ...0 500 0 10 0 700 0 500 0 10 0 K PT100 Voltage VDC Current mA The thermocouple RTD curves are linearised in this microprocessor based product and hence the values interpolated between the readings shown above are also equally accurate at every point in the curve Unit is accepted as accuracy is within the specified limit of claimed accuracy and certificate is valid up to one year from the date of is...

Reviews: