Preface 

This manual describes the M8100 Synchroscope with built-in check synchronizer relay and dead 
bus closure function. 

 

2

 

Function 

The M8100 Synchroscope provides illuminated indication of the actual phase difference between 
generator voltage and bus voltage. If the vector and the light spot turn clockwise, the generator 
frequency is too high and must be reduced. The light spot turning anti clockwise indicates a lower 
generator frequency, and consequently it must be increased. 

In case the generator and busbar voltage and frequency and phase angle are within acceptable 
limits, the built-in check synchronizer relay will activate. The limits of above parameters can be 
adjusted by a potentiometer on the rear side of the unit. 

For clearing of blackout situations the M8100 Synchroscope can be set up to connect a live 
generator to a dead busbar (dead busbar closure function). When enabled, the M8100 Synchroscope 
will give a close command to the generator breaker in case it detects that the busbar voltage is 
below dead busbar voltage offset limit and the generator has reached at least 80% of its nominal 
voltage. The busbar must be dead during the entire dead busbar delay time (this time delay is also 
adjustable). The purpose of the dead busbar voltage offset is to give room for possible noise on the 
busbar voltage input of M8100 Synchroscope. 

Warning:

 As this function could lead to short circuits (e.g. when more than one generator are 

connecting to a dead busbar at the same time, this function should be treated carefully.  

3

 

Connections 

 

Before commissioning, make sure that the 
phase sequences of generator and busbar 
connections are correct. 

 

 

 

 

 

 

 

 

 

Summary of Contents for M8100.0060

Page 1: ...M8196 72E Page 1 of 7 M8100 Synchroscope User Manual SELCO Betonvej 11 DK 4000 Roskilde Denmark Phone 45 7026 1122 Fax 45 7026 2522 e mail selco selco com Web site www selco com...

Page 2: ...2 of 7 Table of contents 1 Preface 3 2 Function 3 3 Connections 3 4 Adjustments 4 4 1 Check synchronizer relay 4 4 2 Dead bus closure 5 4 2 1 Voltage Offset 5 4 2 2 Dead busbar delay time 5 5 Specific...

Page 3: ...on the rear side of the unit For clearing of blackout situations the M8100 Synchroscope can be set up to connect a live generator to a dead busbar dead busbar closure function When enabled the M8100 S...

Page 4: ...busbar voltage are within limits for automatic closure or a pulse signal of 0 4 or 0 8s S1 pin1 OFF pulse signal S1 pin1 ON constant signal In case S1 pin1 is in OFF position S1 pin2 can be used for...

Page 5: ...is to give room for possible noise on the busbar voltage input of M8100 Synchroscope The M8100 Synchroscope considers the busbar to be dead in case the busbar voltage is below the dead busbar voltage...

Page 6: ...classification societies Burn in 50 hours before final test Enclosure material Flame retardant Weight 0 7kg Dimensions 96 x 96 x 80mm H x W x D Panel cut out 92 x 92mm H x W Check sync relay Voltage...

Page 7: ...erminals 1 3 2 3 Type 4 6 5 6 Function M8100 0050 450V 400V With check synchronizer relay M8100 0060 230V With check synchronizer relay M8100 0070 480V 415V With check synchronizer relay M8100 0080 11...