Sel SEL-WCS Manual Download Page 5

5

Date Code 20191014

Information Sheet

SEL-734W and SEL-WCS

Product Overview

Phase identification Settings

The SEL-WCS uses two DIP switches to configure the phase information. 

Table 3

 shows the phase identification settings.

                    

SEL-734W Settings

The Network ID must match the Network ID setting for the SEL-WCSs used 
with this SEL-734W. The other settings on the 734W are explained below.

Voltage Phases

The Voltage Phases setting is used to allow the SEL-734W to calculate power, 
VAs, and VARs for all three phases when the SEL-734W is only sensing a single-
phase voltage. This is done by reusing the magnitude of the measured voltage 
phase, but rotating by ±120 degrees to get the two missing voltage phases. SW1 
of the system setting DIP switches sets this option. When the switch is moved to 
the down position, the SEL-734W only has single-phase data available.

Distance to Sensor

The Distance to Sensor setting is used to ensure that an SEL-734W does not hear 
data from an SEL-WCS on the system that has reused the Network ID of the 
SEL-WCS associated with this SEL-734W. This happens where there are more 
SEL-734Ws in a limited area than the 16 available Network IDs. Although 
unlikely, under ideal conditions, an SEL-734W can receive data from an 
SEL-WCS that is farther than a mile away. This setting reduces the sensitivity of 
the SEL-734W radio receiver so it will not receive data from distant SEL-WCSs.

Line Current Range

The Line Current Range setting refers to the maximum current expected to flow 
in the line during normal (non-fault) conditions. It is used to increase the resolu-
tion of the current reported to the SEL-734W. When in the > 200 A range, the 
resolution is approximately 0.25 A. For the lower range setting, the resolution is 
approximately 0.05 A.

                    

Table 3

Phase Identification Configuration

Switch Settings

Phase

00

A

01

B

10

C

11

Reserved

                    

Figure 4

SEL-734W DIP Switch Settings

Summary of Contents for SEL-WCS

Page 1: ...w the SEL 734W and the SEL 734B differ refer to the sections below SEL Wireless Current Sensor SEL WCS Overview The SEL WCS provides measurement of power line current both for the funda mental frequen...

Page 2: ...allows the SEL WCS to be mounted on the line or removed from the line using only a shotgun stick The springs simplify installa tion on overhead lines and hold the SEL WCS in position See SEL WCS Inst...

Page 3: ...L 734W Figure 2 shows an SEL 734W The orange rectangle in the figure indicates the switches where you make the different settings from those on the SEL 734B Settings Settings are made on both the SEL...

Page 4: ...associated with each Network ID DIP switches SW1 SW4 shown in Figure 2 are for the Network ID Harmonic Content DIP Switch Setting DIP switch SW7 configures the SEL WCS whether it calculates and sends...

Page 5: ...ta available Distance to Sensor The Distance to Sensor setting is used to ensure that an SEL 734W does not hear data from an SEL WCS on the system that has reused the Network ID of the SEL WCS associa...

Page 6: ...ce is closed around the line The spring mechanism should be pushed in so that it wraps around the line Step 3 Apply slight upward pressure until the device is secured around the line as shown in Figur...

Page 7: ...may be impaired This device complies with Industry Canada license exempt RSS standard s Operation is subject to the following two conditions 1 this device may not cause interference and 2 this device...

Page 8: ...ical shock resulting in injury or death DANGER D brancher tous les raccordements externes avant d ouvrir cet appa reil Tout contact avec des tensions ou courants internes l appareil peut causer un cho...

Page 9: ...self your work surface and this equip ment before removing any cover from this equipment If your facility is not equipped to work with these components contact SEL about returning this device and rela...

Page 10: ...odulation FSK Link Range TBD Type Tests Electromagnetic Compatibility Emissions Radiated 47 CFR Part 15 109 Class A Conducted 47 CFR Part 15 107 Class A Electromagnetic Compatibility Immunity Electros...

Page 11: ...ate Code 20191014 Information Sheet SEL 734W and SEL WCS SEL WCS Specifications Table 2 Certifications by Country Country Part Number Authority Reference U S A and Colombia TBD FCC TBD Canada TBD IC T...

Reviews: