SEL Application Guide 2015-33 

 

Date Code 20151102 

Step 6 

Select the 

Configuration Settings

 menu and ensure that 

Factory Logic

 is set to 

Y

, as shown in 

Figure 5. 

 

Figure 5  Configuration Settings 

Step 7 

Select the 

Phase Instantaneous Overcurrent

 menu and set

 Maximum Phase IOC 1 Pickup 

(50P1P)

 equal to the phase instantaneous pickup, as shown in Figure 6. The instantaneous delay 

can be adjusted using 

Maximum Phase IOC 1 Delay (50P1D)

. Modifications to factory logic 

are necessary to set the instantaneous delay below 0.10 seconds. 
Repeat this process for instantaneous ground fault protection by selecting the 

Residual 

Instantaneous Overcurrent

 menu and setting

 Residual IOC 1 Pickup (50G1P)

 and 

Residual 

IOC 1 Delay (50G1D)

. The phase and residual instantaneous overcurrent settings should be 

determined by a power system protective device coordination study. 

 

Figure 6  Instantaneous Overcurrent Settings 

 

 