U.6.38
SEL-421/SEL-421-1 Relay
User’s Guide
Date Code 20020501
Testing and Troubleshooting
Relay Self-Tests
“Release”). For example, in
, the firmware
version number is R101. SEL numbers subsequent firmware releases
sequentially; the next revision following R101 is R102. See
Firmware Versions in the User’s Guide
for firmware version information.
Figure 6.32
Relay Status:
AC
SEL
ERATOR
HMI.
=
>>
STA A<Enter>
Relay 1 Date: 03/15/2001 Time: 04:48:49.938
Station A Serial Number: 2001001234
FID
=
SEL-421-R101-V0-Z001001-D20010315 CID
=
0x4572
Failures
No Failures
Warnings
No Warnings
Channel Offsets (mV) W
=
Warn F
=
Fail
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10 CH11 CH12 MOF
0 0 0 0 0 0 0 0 0 0 0 0 0
Power Supply Voltages (V) W
=
Warn F
=
Fail
3.3V_PS 5V_PS N5V_PS 15V_PS N15V_PS
3.28 4.91 -4.93 14.70 -14.79
Temperature
23.7 degrees Celsius
Communication Interfaces
Active High Accuracy Time Synchronization Source: PPS/IRIG-B
PPS/IRIG-B Source PRESENT
IRIG-B Source PRESENT
Fast Fiber Source ABSENT
SELogic Relay Programming Environment Errors
No Errors
Relay Enabled
=
>>
Figure 6.33
Relay Status From a STATUS A Command on a Terminal.