background image

Schweitzer Engineering Laboratories, Inc.

SEL-2241 Data Sheet

Each SEL Axion

®

 system requires an RTAC module to serve as the system CPU. The SEL-2241 RTAC has all of the

communications and custom logic capabilities of the standalone RTAC modules, but is mounted in and receives power
from the Axion backplane.

Front-Panel

The following figure shows the RTAC status LEDs that
aid system troubleshooting and the connectors for com-
munications and wiring.

Figure 1

SEL-2241 RTAC Front Panel, Copper Ethernet

Mechanical Installation

Each SEL-2242 chassis/backplane has ten slots, labeled

A

 through 

J

. Only Slot 

A

 supports the SEL-2241 RTAC

module.

To install the RTAC, tip the top of the module away from
the chassis, align the notch on the bottom of the module
with Slot 

A

 of the chassis, and place the module on the

bottom lip of the chassis as 

Figure 2

 illustrates. The

module is aligned properly when it rests entirely on the
lip of the chassis.

Figure 2

Proper Module Placement

Next, carefully rotate the module into the chassis, mak-
ing sure that the alignment pin fits into the corresponding
slot at the top of the chassis (refer to 

Figure 3

). Finally,

press the module firmly into the chassis and tighten the
chassis retaining screw.

SEL-2241 Real-Time Automation 
Controller (RTAC)

Summary of Contents for SEL-2241

Page 1: ...2242 chassis backplane has ten slots labeled A through J Only Slot A supports the SEL 2241 RTAC module To install the RTAC tip the top of the module away from the chassis align the notch on the bottom...

Page 2: ...eb interface through the USB cable See Section 7 Security and Account Management in the ACSELERATOR RTAC SEL 5033 Instruction Manual for RTAC web password setup The SEL 2241 has four nonisolated seria...

Page 3: ...ection 1 Getting Started in the SEL 5033 Instruction Manual for instructions on how to back up and restore RTAC projects Step 2 De energize any power source connected to the power coupler s in the Axi...

Page 4: ...ection 3 Factory Reset in the SEL 2240 Instruction Manual describes Table 3 shows the configurable jumper positions SEL 2241 Disassembly To disassemble the SEL 2241 RTAC perform the fol lowing steps S...

Page 5: ...EtherNet IP Explicit Message Client Server DNP3 Serial DNP3 LAN WAN Modbus RTU Modbus TCP SEL Fast Messaging LG 8979 SES 92 IEEE C37 118 IEC 61850 MMS IEC 60870 5 101 104 FTP SFTP CDC Type II EtherNe...

Page 6: ...Ithe Rating 5 A Rated Frequency 50 60 5 Hz Operating Time coil energization to contact closure resistive load Pickup Dropout time 8 ms typical Electrical Durability Make VA Rating 3600 VA cos 0 3 Elec...

Page 7: ...Power Supply Immunity IEC 61000 4 11 2004 IEC 61000 4 29 2000 IEC 60255 11 2008 Magnetic Field Immunity IEC 61000 4 8 2009 Severity Level 1000 A m for 3 seconds 100 A m for 1 minute IEC 61000 4 10 200...

Page 8: ...oducts including without lim itation software firmware and documentation The information in this document is provided for informational use only and is subject to change without notice Schweitzer Engi...

Reviews: