7.23
Date Code 20100129
Instruction Manual
SEL-751A Relay
Communications
SEL ASCII Protocol and Commands
➤
Parity error
➤
Overrun
➤
Re-sync
➤
Data error
➤
Loopback
➤
Underrun
CONTROL Command (Control Remote Bit)
Use the
CON
command (see
) to control remote bits (Relay Word
bits RB01–RB32). You can use the
CON
function from the front panel
(
Control > Outputs
) to pulse the outputs. Remote bits are device variables
that you set via serial port communication only; you cannot navigate Remote
Bits via the front-panel HMI. You can select the control operation from three
states: set, clear, or pulse, as described in
.
Table 7.9
COM Command
Command
Description
Access Level
COM S A
or
COM S B
Return a summary report of the last 255 records in
the communications buffer for either M
IRRORED
B
ITS
communications Channel A or Channel B
when only one channel is enabled.
1
COM A
Return a summary report of the last 255 records in
the communications buffer for M
IRRORED
B
ITS
communications Channel A.
1
COM B
Return a summary report of the last 255 records in
the communications buffer for M
IRRORED
B
ITS
communications Channel B.
1
COM L A
Appends a long report to the summary report of the
last 255 records in the communications buffer for
M
IRRORED
B
ITS
communications Channel A.
1
COM L B
Appends a long report to the summary report of the
last 255 records in the communications buffer for
M
IRRORED
B
ITS
communications Channel B.
1
COM C
Clears all communications records. If both M
IR
-
RORED
B
ITS
channels are enabled, omitting the
channel specifier (A or B) clears both channels.
1
COM C A
Clears all communications records for Channel A.
1
COM C B
Clears all communications records for Channel B.
1
Table 7.10
CONTROL Command
Command
Description
Access Level
CON RB
nn
a
k
b
a
Parameter
nn
is a number from 01 to 32, representing RB01 through RB32.
b
Parameter
k
is S, C, or P.
Set a Remote Bit to set, clear, or pulse.
2
Table 7.11
Three Remote Bit States
Subcommand
Description
Access Level
S
Set Remote bit (ON position)
2
C
Clear Remote bit (OFF position)
2
P
Pulse Remote bit for 1/4 cycle (MOMENTARY
position)
2
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...