5.22
SEL-751A Relay
Instruction Manual
Date Code 20100129
Metering and Monitoring
Breaker Monitor
25 Percent to 50 Percent Breaker Wear
. The current value changes from 2.5 kA to 12.0 kA. 12.0
kA is interrupted 11 times (11 close/open operations = 24 – 13), pushing the
breaker maintenance curve from the 25 percent wear level to the 50 percent
wear level.
Compare the 100 percent and 50 percent curves and note that for a given
current value, the 50 percent curve has only 1/2 of the close/open operations
of the 100 percent curve.
Figure 5.22
Breaker Monitor Accumulates 50 Percent Wear
10,000
100%
1000
2
3
4
5
6
7
8
9
100
2
3
4
5
6
7
8
9
10
2
3
4
5
6
7
8
9
1
2
3
4
5
6 7 8 9
50
40
30
20
10
.5
Number of Close/Open Operations
kA Interrupted per Operation
25%
50%
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...