5.7
Date Code 20100129
Instruction Manual
SEL-751A Relay
Metering and Monitoring
Metering
shows an example device response to the
METER M
command.
=>>
MET M <Enter>
SEL-751A Date: 12/02/2008 Time: 15:46:02
FEEDER RELAY Time Source: External
MAX DATE TIME MIN DATE TIME
IA (A) 1005.8 12/02/2008 15:41:43 19.8 11/09/2008 03:55:41
IB (A) 1097.1 12/02/2008 15:41:26 197.3 11/16/2008 11:41:10
IC (A) 972.7 12/02/2008 15:45:11 206.0 11/16/2008 11:40:47
IN (A) 0.5 11/11/2008 18:20:00 0.4 11/16/2008 11:39:43
IG (A) 155.9 12/02/2008 15:42:32 0.4 11/12/2008 00:31:39
VAB (V) 6650.4 12/02/2008 15:45:45 6647.4 12/02/2008 15:41:14
VBC (V) 6671.9 12/02/2008 15:42:56 6666.8 12/02/2008 15:39:54
VCA (V) 7505.1 12/02/2008 15:41:05 7502.9 12/02/2008 15:45:42
VS (V) 6741.4 12/02/2008 15:45:11 6647.4 12/02/2008 15:41:14
KW3P (kW) 7797.2 11/11/2008 13:45:15 -11108 12/02/2008 15:41:42
KVAR3P (kVAR) 5031.8 12/02/2008 15:42:49 -1396.3 12/02/2008 15:45:24
KVA3P (kVA) 12187 12/02/2008 15:41:42 608.1 11/16/2008 11:42:27
FREQ (Hz) 60.1 11/16/2008 11:36:54 60.0 12/02/2008 15:45:23
LAST RESET = 11/09/2008 03:54:34
=>>
Figure 5.6
Device Response to the METER M Command
To reset maximum/minimum meter values, issue the
METER RM
command
as shown in
. The max/min meter values can be reset from the serial
port, Modbus, the front panel, or assertion of the RSTMXMN relay element.
The date and time of the reset are preserved and shown in the max/min meter
report.
=>>
MET RM <Enter>
Reset Metering Quantities (Y,N)?
Y
<
Enter
>
Reset Complete
=>>
Figure 5.7
Device Response to the METER RM Command
All maximum and minimum metering values are stored to nonvolatile
memory four times per day and within one minute of the maximum and
minimum metering values being reset.
Math Variable
Metering
The SEL-751A includes 32 math variables. When you receive your
SEL-751A, no math variables are enabled. To use math variables, enable the
number of math variables (between 1 and 32) you require, using the EMV
setting in the Logic setting category.
shows the device response to
the
METER MV M
(ath)
V
(ariable) command with 8 of the 32 math variables
enabled.
=>>
MET MV <Enter>
SEL-751A Date: 04/17/2007 Time: 12:32:10
FEEDER RELAY Time Source: Internal
MV01 1.00
MV02 -32767.00
MV03 -1.00
MV04 0.00
MV05 1000.59
MV06 -1000.61
MV07 2411.01
MV08 2410.99
=>>
Figure 5.8
Device Response to the METER MV Command
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...