This 8-pin (size 22) receptacle provides an eight-pin male receptacle that exits 
from the bottom of the cabinet. The 8-pin cable is internally wired to 300 Vac 
voltage max inputs. The 8-pin receptacle provides a convenient way (by way 
of external cable, which is not included) to connect external potential 
transformer secondary outputs to the control. Depending on the secondary 
input voltage option of your control, you may wire to just the Y-side, just the 
Z-side, or both Y- and Z-side voltage inputs. 

Parts

Installation

Step 1. Install the 8-pin (size 22) voltage input receptacle harness in 

the bottom of the cabinet in the center hole in the back row. See 

Figure 1

.

a. Insert the receptacle harness inside the cabinet and 

insert the four screws from outside. 

b. Install the nuts on the screws from the inside of the 

cabinet. 

Step 2. Install the smaller ring terminal of the green/yellow ground 

wire and the two drain wires to the last connector screw and 
secure them with the last nut. See 

Figure 1

.

Step 3. Use the existing nut to connect the larger ring terminal of the 

green/yellow ground wire to the ground stud. See 

Figure 1

.

SEL Part Number

Description

Quantity

SEL-C2253

8-pin (size 22) voltage input receptacle harness

1

SEL-C5241

Ground wire

1

080-0101

5/8 steel wire clamp

2

140-0500

4-40 x 1/2" screw

4

140-0740

4-40 hex nut

4

144-0140

Plastic cap

1

310-0050

Zip ties

12

SEL-651RA Installation Instructions for 8-Pin 
(Size 22) Receptacle for Voltage Inputs

Summary of Contents for 651RA

Page 1: ...of the cabinet in the center hole in the back row See Figure 1 a Insert the receptacle harness inside the cabinet and insert the four screws from outside b Install the nuts on the screws from the ins...

Page 2: ...he 14 pin connector See Figure 2 Figure 2 Form Drip Loop and Route Harness Wires Step 2 Join the 8 pin wires with the main harness and route the wires through the wire loom and up the swing panel hing...

Page 3: ...at shrink on the ring terminals Figure 4 Attach Wires to Control Module Step 6 Zip tie wires as necessary Table 1 SIV Specific Wiring SIV Option MOT Character Wire Single phase 1 A B C D only Y side 6...

Page 4: ...2 inches of the jacket and strip the individual wires about 7 16 of an inch Step 3 The Z side cable is marked with white heat shrink on the Z side ring terminals to distinguish them from the Y side r...

Page 5: ...8 Pin Black Wire A No Heatshrink Brown Wire B No Heatshrink To Fuse Block V1Y Bottom V2Y Bottom Red Wire C No Heatshrink Orange Wire D No Heatshrink V3Y Bottom NY Bottom Black Wire E Heatshrink Brown...

Page 6: ...SEL 651RA Recloser Control Date Code 20160329 6 Wiring Diagrams Without Fuse Block Ground Stud Drain A B C D E F G H...

Page 7: ...Date Code 20160329 SEL 651RA Recloser Control 7 With Fuse Block Ground Stud Drain Wiring between fuse block and control module not shown H G F E D C B A L1 N1 L2 N2 V1Y V2Y V3Y V2Z V3Z NY GY V1Z NZ GZ...

Page 8: ...ge without notice Schweitzer Engineering Laboratories Inc has approved only the English language document This product is covered by the standard SEL 10 year warranty For warranty details visit selinc...

Reviews: