Date Code 20160329
SEL-651RA Recloser Control
Introduction
This 8-pin (size 22) receptacle provides an eight-pin male receptacle that exits
from the bottom of the cabinet. The 8-pin cable is internally wired to 300 Vac
voltage max inputs. The 8-pin receptacle provides a convenient way (by way
of external cable, which is not included) to connect external potential
transformer secondary outputs to the control. Depending on the secondary
input voltage option of your control, you may wire to just the Y-side, just the
Z-side, or both Y- and Z-side voltage inputs.
Parts
Installation
Step 1. Install the 8-pin (size 22) voltage input receptacle harness in
the bottom of the cabinet in the center hole in the back row. See
Figure 1
.
a. Insert the receptacle harness inside the cabinet and
insert the four screws from outside.
b. Install the nuts on the screws from the inside of the
cabinet.
Step 2. Install the smaller ring terminal of the green/yellow ground
wire and the two drain wires to the last connector screw and
secure them with the last nut. See
Figure 1
.
Step 3. Use the existing nut to connect the larger ring terminal of the
green/yellow ground wire to the ground stud. See
Figure 1
.
SEL Part Number
Description
Quantity
SEL-C2253
8-pin (size 22) voltage input receptacle harness
1
SEL-C5241
Ground wire
1
080-0101
5/8 steel wire clamp
2
140-0500
4-40 x 1/2" screw
4
140-0740
4-40 hex nut
4
144-0140
Plastic cap
1
310-0050
Zip ties
12
SEL-651RA Installation Instructions for 8-Pin
(Size 22) Receptacle for Voltage Inputs