safety temperature is reached, in order to avoid thermal 

shock and air pockets in the system.

The collector pump will automatically restart only if the 

collector temperature measured with sensor TS_1 is below 

the T_SF collector reset temperature.

Collector reset temperature

AFTER SELECTING PARAMETER P10 PRESS

THE ‘ 

  ‘ KEY.

WITH ARROWS ‘ 

 ‘ OR ‘ 

 ‘, YOU CAN CYCLE AMONG 

THE FOLLWOWING DATA FOR REGULATION:
- Enable parameter 

 

 

‘ ENA ‘

- Increase temperature   

 

‘ INC ’

- Pump activation lapse  

 

‘ TIME ’

PRESS THE ‘ 

  ‘ KEY TO MODIFY THE DATA 

SELECTED; THE DATA WILL START FLASHING.

USE THE ‘ 

 ‘ OR ‘ 

 ‘, ARROWS TO SET THE 

DESIRED NUMERIC VALUE.

PRESS THE ‘ 

  ‘ KEY TO CONFIRM THE

PROGRAMMING OR PRESS THE ‘ 

esc

 ’ KEY TO 

CANCEL THE CHANGES.

P10: 

VACUUM TUBES

In some solar systems, for example when vacuum tubes are 

installed, the collector temperature measurement could be 

slow, because of its non optimal position.

By  enabling  the  function  you  can  choose  between  two 

different operating programs:

P_1

 where VTC function is enabled and Boiler safety 

thermostats are prioritized.

P_0

 where VTC function is enabled and both Boiler and 

collector pump safety thermostats are disabled.

By enabling the VTC, the following collector pump control 

is started:

If the collector sensor temperature increases by the amount 

set in the subparameter ‘INC’ within one minute, then the 

collector pump will be operated for the time set in the 

subparameter ‘TIME’.

After the activation of the pump for the time set in the 

subparameter ‘TIME’, the function will be off for 5 minutes.

PRESS ARROWS ‘ 

 ‘ and ‘ 

 ‘ TO SET

THE DESIRED VALUE.

PRESS THE ‘ 

  ‘ KEY TO CONFIRM THE 

PROGRAMMING OR PRESS THE ‘ 

esc

 ’ KEY TO CANCEL 

THE CHANGES.

AFTER SELECTING PARAMETER P9 PRESS

THE ‘ 

  ‘ KEY.

THE DISPLAY SHOWS ‘ T_SF ’.

PRESS ‘ 

  ‘. THE DISPLAY

SHOWS ‘T_SF’ FLASHING.

Data

Regulation range

Default

T_SF

OFF / 60 °C .. 180 °C

OFF

Summary of Contents for TDST24M

Page 1: ...LAR SYSTEMS c The installation technician shall operate in full compliance with all the applicable technical standards in order to grant the unit safety WARNING DESCRIPTION OF THE KEYS RESET KEY MENU...

Page 2: ...C 145 C 180 C Offset adjustment on S1 5 0 C on S2 5 0 C on S3 5 0 C Installer Password 0000 9999 default 0000 Acoustic Signal On Off default On Backlight timing 20 sec from last keypress OUT2 Relay L...

Page 3: ...to pass through and fit the blocks delivered 6 INSTALLATION 2 Remove the two screws shown in the drawing then remove the whole body from the base 5 Fit the cover again with the electronics at the bas...

Page 4: ...obe blue cable must be used while the probes with the range of 50 C 110 C yellow cable can be used for the other probes The outputs OUT1 OUT2 and Alarm are voltage free It is advisable to fit a 10A 25...

Page 5: ...hat the removable wiring terminals have been inserted with the correct orientation the terminals screws must be facing upward EXAMPLE OF CONNECTION FOR 3 SPEED SOLAR CIRCULATORS WITH WET or HIGH EFFIC...

Page 6: ...ow on the alphanumeric display the temperature in C measured by the sensors connected and the speed in of the collector pump controlled with the PWM or 0 10V output The power on of the collector pump...

Page 7: ...ng the Password In order to modify the stored password first press the key then proceed as follows PRESS THE MENU KEY THE DISPLAY SHOWS PWDH0000 Pressing the esc key at any time will exit the password...

Page 8: ...ic hysteresis WARNING The thermal parameters to be set are displayed when the relevant scheme is selected this means the power unit will only display the thermal parameters actually activated for the...

Page 9: ...nstallation with 1 tank and additional thermostatic heating Control logic OUT 1 TS2 TS3 TS1 T1 2 TM3 TAF AFR 1 0 OUT 2 TAH TAH OUT 3 SCH 06 Solar heating installation with 1 tank and only 2 probe Cont...

Page 10: ...0 C TS3 20 0 90 0 C 80 0 C WARNING It is not possible to set the Safety Temperatures TS2 and TS3 to a value lower than the relevant Maximum Temperature as the value of the Safety Temperature is limit...

Page 11: ...ety Temperature TS 5 C To increase the Maximum Temperature value it is first necessary to increase the value of the Safety Temperature Integration Temperature After Heating on probe S3 Data Regulation...

Page 12: ...CTING PARAMETER P3 PRESS THE KEY USE THE OR ARROWS TO SET THE DESIRED NUMERIC VALUE PRESS THE KEY TO CONFIRM THE PROGRAMMING OR PRESS THE esc KEY TO CANCEL THE CHANGES PRESS THE KEY TO MODIFY THE THER...

Page 13: ...he function is not supported by the layout selected the controller will display NONE Note 1 means Normally Open N O logic while 0 means Normally Closed N C logic AFTER SELECTING PARAMETER P5 PRESS THE...

Page 14: ...ion whenever on the relevant panel is measured a temperature lower than the one set in this parameter The function Minimum Temperature Limitation is not active when in ABC operation or in case the pum...

Page 15: ...SET THE DESIRED NUMERIC VALUE PRESS THE KEY TO CONFIRM THE PROGRAMMING OR PRESS THE esc KEY TO CANCEL THE CHANGES In the following the regulation ranges allowed for each parameter are listed Setting...

Page 16: ...NOR set by the parameter ERP P8 PUMP When parameter PUMP NOR PWM2 Tr 0 The pump takes its speed at level OFF or VOFF 0 Tr T The pump will have a variable rotation speed between ON and MAX or between...

Page 17: ...and vice versa in order to prevent abrupt changes or oscillations in the system regulation Fixed mode temperature control Data Regulation range Default T_FT 0 C 90 C 60 C Note this parameter is activ...

Page 18: ...temperature measurement could be slow because of its non optimal position By enabling the function you can choose between two different operating programs P_1 where VTC function is enabled and Boiler...

Page 19: ...ella function The anti Legionella function activated by default consists of a boiler s water heating cycle at 65 C every 30 days for 5 minutes in order to carry out thermal disinfection action against...

Page 20: ...erential value is fixedto 2 C therefore not adjustable FUNCTIONS ACCESSIBLE TO THE USER The functions accessible to the user are limited and do not allow setting those data influencing the installatio...

Page 21: ...OWING THE USER PARAMETERS PRESSING RESETS THE TEMPERATURE RECORDED TO THAT POINT PRESSING esc RETURNS TO SHOWING THE MEMORIZED TEMPERATURE PRESS THE esc KEY TO QUIT THE MAXIMUM TEMPERATURE DISPLAY MOD...

Page 22: ...d by a series of beeps together with the quick flashing of the red power supply led The probe originating the problem is flashing on the display The control unit has revealed an anomaly on the probe T...

Page 23: ...23 TDST24M000SE 032635 190619 NOTE...

Page 24: ...24 TDST24M000SE 032635 190619 SEITRON S p A a socio unico Via del Commercio 9 11 36065 Mussolente VI ITALY Tel 39 0424 567842 Fax 39 0424 567849 www seitron it info seitron it...

Reviews: