18
protect both
the room and the equipment when the room temperature
falls below the set value.
The parameter can be set in the range OFF, 0,5°C .. 25°C.
The device leaves the factory with the Antifreeze function set on
3°C.
IMPORTANT: the function is active only when the device has
been set in the heating mode.
‘
OFS1
’ INTERNAL SENSOR OFFSET SETTING
With this parameter it is possible to correct the temperature reading
of the internal sensor by ±5°C in order to correct any systematic
reading errors due to the positioning of the programmable thermostat
in areas unsuitable for measuring the room temperature.
The device leaves the factory with the Offset set at 0.0°C.
‘
OFS2
’ REMOTE SENSOR OFFSET SETTING
With this parameter it is possible to correct the temperature reading
of the remote sensor by ±5°C in order to correct any systematic
reading errors due to the positioning of the remote sensor in areas
unsuitable for measuring the room temperature.
The device leaves the factory with the Offset set at 0.0°C.
‘
rEG
’ REGULATION SENSOR CHOICE SETTING
This parameter sets whether the room temperature regulation is
made based on the programmable thermostat internal sensor or the
remote sensor, wired at terminals 8 and 9.
For this parameter setting please find these directions:
1.
Select parameter ‘
rEG
’ then press key ‘
OK
’
Normally, in order to have a reduced temperature at nighttime, knob
‘ ‘
will be set on a lower value than knob
‘ ‘
.
SETTING THE USER PARAMETERS
To enter the mode for setting the programmable thermostat
parameters, proceed as follows:
1.
Press for more than 20 seconds the key ‘
‘; the display will
show the first user parameter ‘
AFr
‘.
2.
Press the ‘
‘ button repeatedly to scroll through the user
parameters:
Antifreeze Setting
‘
AFr
’
Internal sensor Offset setting
‘
OFS1
’
Remote sensor Offset setting
‘
OFS2
’
Regulation sensor choice setting
‘
rEG
’
Hysteresis setting
‘
HYS
’
PWM output setting
‘
OPWM
’
Set default data
‘
dFLt
’
3.
Press the ‘
OK
’ button to modify the selected parameter.
4.
Set the data related to every single parameter, pushing the buttons
‘
’ and ‘ ‘
;
every change will be automatically
stored in memory
.
5.
To exit the user parameter programming mode, press the
‘
’
button to confirm the changes made or else wait 10 seconds
without pressing any button.
‘
AFr
’ ANTIFREEZE SETTING
The Antifreeze function allows you to select a minimum temperature
to be maintained when the programmable thermostat is off, so as to