background image

TAG02M0000SE 035670 161120

7

OPERATION

STARTING UP

When first operating:

-  Perform the electrical connections as explained on the wiring 

diagram proposed on the chapter “Electrical wirings”.

-  Power on the device.

-  Set time and day of the current week.

-  Set  the  operating  mode  of  the  programmable  thermostat 

(user parameter ‘C-H’): Heating (factory default) or Cooling.

SETTING THE CURRENT TIME AND DAY

To set the clock of the programmable thermostat carry out the 

following steps:

1.

  Keep the ‘

OK

’ button pressed for at least 3 seconds; the 

hour digits will start flashing.

2.

  Set the hour using buttons ‘ 

 ‘ and ‘   ‘.

3.

  Confirm by pressing ‘

OK

’; the minute digits will start flashing.

4.

  Set the minutes using buttons ‘ 

 ‘ and ‘   ‘.

5.

  Confirm with ‘

OK

’; the display shows alternatively the writing 

‘MtH’ and the number related to the month.

6.

  Set the current month with buttons ‘ 

 ‘ and ‘   ‘.

7.

  Confirm with ‘

OK

’; the display shows alternatively the writing 

‘day’ and the number related to the current day.

8.

  Set the current day with the buttons ‘ 

 ‘ and ‘   ‘.

9.

  Confirm with ‘

OK

’; the display shows alternatively the writing 

‘yea’ and the number related to the current year.

10.

 Set the current year with buttons ‘ 

 ‘ and ‘   ‘.

11.

 Confirm by pressing ‘

OK

’; the output of the time and day 

setting is automatic.

COMFORT AND ECONOMY TEMPERATURES ADJUSTMENT

During  normal  operation,  the  display  shows  the  measured 

room  temperature  and  the  icon  for  the  current  setting  mode        

‘   ‘ or ‘   ‘.

In  order  to  display  the  relevant  set-point  temperature,  press 

once the button ‘ 

 ’ or ‘ 

 ’: the display shows the set-point 

temperature,  the  icon  ‘

SET °C

‘  (meaning  that  the  setpoint 

temperature is being displayed) and icon ‘ 

 ‘ or ‘   ‘ depending 

on  whether  the  programmable  thermostat  is  regulating  in 

comfort mode or economy mode.

By pressing the ‘ 

 ’ and ‘ 

 ’ buttons, the displayed setpoint 

temperature can be changed.

By pressing the ‘   ‘ button while the display is showing the 

‘Comfort’  setpoint  temperature,  the  display  changes  to  show 

the  ‘Economy’  temperature.  Vice  versa,  if  the  display  was 

showing the ‘Economy’ set point, by pressing the ‘ 

 ‘ button, 

the display changes to show the ‘Comfort’ set point.

By pressing the 

OK

‘ or 

after a few seconds of inactivity, the 

display returns to show the room temperature.

Note: Usually, in order to get a temperature reduction in night 

time, the economy temperature should have a value lower 

than the comfort one.

The programmable thermostat will then adjust the temperature 

in comfort mode or economy mode according to the set time 

schedule (see ‘SET USER PARAMETERS’).

SETTING THE LIMITS TO REGULATE THE SET POINT 

TEMPERATURE

In order to modify the limits of the set-point temperature setting 

proceed as follows: 

1. 

Turn off the programmable thermostat by pressing the button 

‘   ‘.

2.

 Cut off the power voltage and wait a few seconds.

3.

 Power on the programmable thermostat and when the display 

shows the writing OFF, press at the same time (whithin 30 

seconds) the buttons ‘ 

 ‘ and ‘   ‘.

4.

 The display shows the icon ‘ SET °C’ which is the first data to 

modify.

TAG02M

DIGITAL WEEKLY PROGRAMMABLE THERMOSTAT FOR 

GREENHOUSES, WITH TWO STAGES AND FAN OUTPUT

Via del Commercio, 9/11. 36065 Mussolente (VI) ITALY

Tel.: +39.0424.567842 - Fax.: +39.0424.567849

http://www.seitron.com - e-mail: [email protected] 

GENERALITIES

This  device  is  a  weekly  digital  programmable  thermostat 

powered with 230V , for room temperature control on three 

stages  (Comfort,  Economy  or  Off/Antifrost)  which  allows 

to manage, on full automatic mode, double-power version 

devices,  double-stage  and  one-stage,  with  the  possibility  to 

activate the second stage at the same time with the first one 

for a maximum of 200 seconds. A third relay output is available 

and managed only in cooling mode, for the activation of a fan.

Furthermore  this  device  is  featured  with  a  reset  circuit  for 

burners  with  block  signaling  and  reset  button,  electrically 

separated  from  the  programmable  thermostat.  This  device 

can  be  used  either  on  heating  and  cooling  systems.  The 

programmable thermostat is featured with a wide backlit display 

in order to view all the operational conditions, the hourly set 

program,  room  temperature  detected  by  the  external  sensor 

or, if chosen, the current time. It offers the possibility to set up 

to 7 different programs, one for each week day, with minimum 

intervention time of 1/2 hour within 24 hours.

WARNING!

The product is not featured with an internal temperature 

sensor so it is necessary to connect a remote temperature 

sensor (not provided, for further details see paragraph 

“Accessories and spare parts”).

DESCRIPTION OF CONTROLS

LEGEND

A

  Double function button:

-  In  normal  operation:  turns  on  and  off  the  programmable 

thermostat.

-  In schedule programming: sets the regulation temperature 

into Off / Antifreeze mode.

B

  Double function button:

-  In normal operation: activates the function 24 hours Manual 

/ Permanent Manual / Automatic.

-  In schedule programming: sets the regulation temperature 

into Economy mode.

C

  Triple function button:

-  In normal operation: displays current time or temperature.

-  In schedule programming: sets the regulation temperature 

on Comfort mode.

-  In  ‘Set-Point  temperature  settings’,  shows  either  the 

Comfort or the Economy temperature.

D

  Forward/setting button (by increasing the value) for the set 

point temperature.

E

  Back/setting button (by decreasing the value) for the set point 

temperature.

F

  OK button (confirm).

Programming button: enters the programming menu.

H

  Reset button.

I

 LED.

A

B

C

D

E

F

H

I

G

Summary of Contents for TAG02M

Page 1: ...onamento del cronotermostato parametro utente H C Riscaldamento impostato in fabbrica o Raffrescamento REGOLAZIONE ORA E GIORNO CORRENTE Per regolare l orologio del cronotermostato eseguire le seguenti operazioni 1 Tenere premuto per almeno 3 secondi il pulsante OK le cifre dell ora lampeggiano 2 Regolare l ora con i tasti e 3 Confermare con OK le cifre dei minuti lampeggiano 4 Regolare i minuti c...

Page 2: ...cceso interno Modalità di comfort due trattini accesi Modalità spento antigelo nessun trattino acceso Giorni della settimana 1 Lunedì 7 Domenica Il quadratino indica il giorno o il gruppo di giorni corrente Per impostare il programma orario proseguire come descritto nel seguito Nota Si uscirà dalla regolazione senza memorizzare il programma impostato se per più di 10 secondi non si preme alcun tas...

Page 3: ... visualizza la temperatura precedentemente impostata e l icona P lampeggiante 3 Premere i tasti e per modificare il valore compreso tra 0 1 C 15 C ogni modifica viene memorizzata automaticamente 4 Per ritornare alla lista dei parametri utente premere il tasto OK 5 Per uscire dall impostazione dei parametri utente e ripristinare il normale funzionamento premere il tasto oppure attendere 10 secondi ...

Page 4: ...00 8 00 8 00 11 00 11 00 13 00 13 00 17 00 17 00 23 00 23 00 6 00 AFr 3 0 C d1 0 2 C d2 0 2 C d12 3 0 C tMr2 0 secondi OFS1 5 C H C HEAt riscaldamento StM EnA abilitato ATTENZIONE L impostazione dei Dati di Default non modifica i valori precedentemente impostati di Ora e data Set Point e i limiti minimi e massimi impostabili dei SET POINT stessi Procedere come segue 1 Selezionare il parametro dFLt...

Page 5: ... ambiente rilevata dalla sonda remota La temperatura rilevata viene visualizzata corretta dal valore di Offset impostato Nel caso in cui la sonda remota non è stata collegata o è danneggiata il display visualizzarà rispettivamente la scritta SEnS OPEN oppure SEnS SHrt con l icona lampeggiante RETROILLUMINAZIONE L accensione della retroilluminazione del display si verifica in seguito alla pressione...

Page 6: ...collegamento elettrico del dispositivo devono essere eseguiti da personale qualificato ed in conformità alle leggi vigenti Prima di effettuare qualsiasi collegamento accertarsi che la rete elettrica sia scollegata GARANZIA Nell ottica di un continuo sviluppo dei propri prodotti il costruttore si riserva il diritto di apportare modifiche a dati tecnici e prestazioni senza preavviso Il consumatore è...

Page 7: ...tting proceed as follows 1 Turn off the programmable thermostat by pressing the button 2 Cut off the power voltage and wait a few seconds 3 Power on the programmable thermostat and when the display shows the writing OFF press at the same time whithin 30 seconds the buttons and 4 The display shows the icon SET C which is the first data to modify TAG02M DIGITAL WEEKLY PROGRAMMABLE THERMOSTAT FOR GRE...

Page 8: ...it Off Antifreeze mode no dashes lit Days of the week 1 Monday 7 Sunday The box indicates the current day or group of days To set the program schedule proceed as described below Note You will exit the programming mode without memorizing the programmed schedule if more than 10 seconds elapse and you do not press any button or else you can confirm the settings in sequence by pressing the OK button w...

Page 9: ...odify the value included in 0 1 C 15 C every update is stored automatically 4 In order to go back to the user parameters list push the OK button 5 To exit from the setting of the user parameters and reset the normal operation push the button or wait 10 seconds without pushing any button d12 SETTING THE DIFFERENTIAL BETWEEN FIRST AND SECOND STAGE The setting of this parameter allows to define the v...

Page 10: ... The Default Data setting does not modify the values previously set of Time and date Set Point and settable minimum and maximum limits of the SET POINTs themselves Proceed as follows 1 Select the parameter dFLt and press OK the device automatically sets the default data and the display will show dF and the P icon flashes 2 To quit the user parameter settings press the OK button or wait 10 seconds ...

Page 11: ...he display cycles on showing the current time and the room temperature measured by the remote sensor The values of temperature displayed are shown adjusted with the set Offset value In case the remote sensor is not wired or is broken the display will show the words SEnS OPEN or SEnS SHrt with the blinking icon BACKLIGHTING The display backlight turns on whenever and button is pressed It turns off ...

Page 12: ...irings of this appliance must be made by qualified technicians and in compliance with the current standards Before wiring the appliance be sure to turn the mains power off WARRANTY n the view of a constant development of their products the manufacturer reserves the right for changing technical data and features without prior notice The consumer is guaranteed against any lack of conformity accordin...