- ENGLISH -

THW02B0000SE 027077 070616

2

programmed.

  In the following the four available combinations are listed:

(Mo)

2nd combination

of days

7

2

3

4

5

6

1

1st combination

of days

7

6

2

3

4

5

1

2

3

4

5

6

7

1

4th combination

of days

(Schedule

Day by Day)

5

6

7

1

2

3

4

3rd combination

of days

(Fr

(Th)

(We)

(To)

(Su)

(Sa)

Note: For each day combination, the time schedule set will be 

the same for all days within each single group.

3.

 Press the ‘ 

OK

 ‘ button to confirm the setting made; the display will 

show the schedule previously programmed for the set day or group 

of days and the time 00.00 (cursor flashing on the interval between 

00.00 and 00.30).

4.

 Set the operating mode.

  To facilitate the programming operation, the thermostat is factory 

preset with the following time intervals:

TIME INTERVALS PRESET

Comfort mode

Economy mode

6.00 .. 8.00

8.00 .. 11.00

11.00 .. 13.00

13.00 .. 17.00

17.00 .. 23.00

23.00 .. 6.00

 

Alternatively,  if  the  preset  time  interval  doesn’t  fit  the  required 

needs, you can change it manually as follows:

5.

 For every time interval (each dash corresponds to a half hour) set 

the operating mode by pressing one of the following buttons:

 

Comfort mode

Press the ‘ 

 ‘ button.

 

Off / Antifreeze

Press the ‘   ‘ button.

 

Economy mode

Press the ‘   ‘ button.

 

Moving the time cursor

Press button ‘   ’ or ‘   ‘.

Conferma

Riduzione

Spento

Comfort

  Each time the button which sets the regulation mode is depressed, 

the time cursor automatically jumps into the next half hour.

6.

 After programming the schedule for the day or group of days 

selected, press the ‘ 

OK

 ’ button.

  The  display will show the  program  schedule for  the  next  day or 

groups of days until the whole week is covered.

7.

 After programming the schedule for the entire week, press the ‘ 

OK 

’ button. The programmable thermo-hygrostat will memorize the 

schedule set and the word ‘

MEMO

’ will appear on the display; the 

device will automatically exit the schedule programming mode.

WARNING

-  If you want to reset the time intervals to factory settings, 

please reach the user parameter ’ dFLt ’ (the default data); In 

this case, all user parameters will be reset to factory settings. 

-  If you exit the time programming without pressing the ’ OK ’ 

button, or you do not save the settings, the time program will 

NOT be saved in memory and the previous program will be 

restored.

  Changes are stored in memory only when the if you enable 

this operation with the phase characterized by the word 

’MEMO’.

‘ 

AFr 

’ ANTIFREEZE SETTING

The Antifreeze function allows you to select a minimum temperature to 

be maintained when the programmable thermo-hygrostat is off, so as to 

protect both the room and the equipment when the room temperature 

falls below the set value. The device leaves the factory with the 

Antifreeze function set on 3°C.

IMPORTANT: the function is active only when the device has 

been set in the heating mode.

To set the Antifreeze temperature, carry out the following steps:

1.

 Select the parameter ‘ 

AFr 

’ and press the ‘ 

OK 

’ button.

2.

 The display shows the Antifrost temperature previously set and the 

‘ 

P

 

‘ icon flashes.

3.

 Press buttons ‘   ‘ and ‘   ‘ to change the setting (between OFF, 

0.5°C..25°C); every change will be automatically memorized.

4.

 To return to the list of user parameters, press the ‘

OK

’ button.

5.

 To exit the user parameters setting and resume normal operation, 

press the ‘   ‘ button or wait 10 seconds without pressing any 

key.

HYS

’ SETTING THE HYSTERESIS

Setting this parameter allows to define the hysteresis, in °C, which 

is applied to the programmable thermo-hygrostat to adjust the room 

temperature, whenever the ‘ 

C-dP

 ‘ (dew point) user parameter has 

not been enabled.

To adjust the hysteresis perform the following steps:

1.

 Select the parameter ‘ 

HYS 

’ and press ‘ 

OK 

’.

2.

 The display shows the previously set temperature and the ‘ 

P

 

‘ 

icon flashes.

3.

 Press the ‘   ‘ and ‘    ‘  to  change  the  value  (between                             

0.1 °C .. 5.0 °C); 

each change is automatically saved

.

4.

 To return to the list of user parameters, press the ‘

OK

’ button.

5.

 To exit the user parameter settings and resume normal operation, 

press the ‘   ‘ button or wait 10 seconds without pressing any key.

‘ 

OPt

 ’ OPTIMIZATION SETTING

The optimization function consists in the option of turning on the 

heating or cooling earlier than the scheduled time in order to reach the 

set temperature by the scheduled time.

The programmable thermo-hygrostat calculates the time necessary 

in order to reach the desired temperature and turns on the heating 

in advance accordingly, by the amount of time necessary to achieve 

the target.

The amount of time in advance may be 60 minutes at most and is 

calculated based on the average gradient of the previous 24 hours.

To set the optimization function carry out the following steps:

1.

 Select the parameter ‘

OPt

’ and press the ‘

OK

’ button.

2.

 The display shows ‘on’ or ‘Off’ and the ‘ 

P

 

‘ icon flashes.

3.

 Press button ‘   ‘ to activate (On) or ‘   ‘ to deactivate (Off) the 

function; 

every change will be automatically memorized

.

4.

 To return to the list of user parameters, press the ‘

OK

’ button.

5.

 To exit the user parameter settings and resume normal operation, 

press the ‘   ‘ button or wait 10 seconds without pressing any key.

‘ 

OFS1 

’ INTERNAL SENSOR OFFSET SETTING

With this parameter it is possible to correct the temperature reading 

of the internal sensor by ±5°C in order to correct any systematic 

reading errors due to the positioning of the programmable thermo-

hygrostat in areas unsuitable for measuring the room temperature. 

The device leaves the factory with the Offset set at 0.0°C.

To adjust the Offset value for the internal sensor, carry out the 

following steps:

1.

 Select the ‘ 

OFS1

 ’ parameter and press the ‘ 

OK

 ’ button.

2.

  The  display  shows  the  Offset  temperature  previously  set  and  the          

‘ 

P

 

‘ icon flashes.

3.

 Press buttons ‘   ‘ and ‘    ‘  to  modify  the  setting  (range:               

-5.0°C .. +5.0°C); 

every change will be automatically stored 

in memory

.

4.

 To return to the list of user parameters, press the ‘

OK

’ button.

5.

 To exit the user parameter settings and resume normal operation, 

press the ‘   ‘ button or wait 10 seconds without pressing any key.

‘ 

OFS2 

’ REMOTE SENSOR OFFSET SETTING

With this parameter it is possible to correct the temperature reading of 

the remote sensor by ±5°C in order to correct any systematic reading 

errors due to the positioning of the remote sensor in areas unsuitable 

for measuring the room temperature. The device leaves the factory 

with the Offset set at 0.0°C.

To adjust the Offset value for the remote sensor, carry out the 

following steps:

1.

 Select the ‘ 

OFS1

 ’ parameter and press the ‘ 

OK

 ’ button.

2.

  The  display  shows  the  Offset  temperature  previously  set  and  the          

‘ 

P

 

‘ icon flashes.

3.

 Press buttons ‘   ‘ and ‘    ‘  to  modify  the  setting  (range:               

-5.0°C .. +5.0°C); 

every change will be automatically stored 

in memory

.

4.

 To return to the list of user parameters, press the ‘

OK

’ button.

5.

 To exit the user parameter settings and resume normal operation, 

press the ‘   ‘ button or wait 10 seconds without pressing any key.

‘ 

rEG 

’ REGULATION SENSOR CHOICE SETTING

This parameter sets whether the room temperature regulation is made 

based on the programmable thermo-hygrostat internal sensor or the 

remote sensor connected to the connector ‘ 

B

 ‘ in Fig. 6.

For this parameter setting please find these directions:

1. 

Select parameter ‘ 

rEG

 ’ then press key ‘ 

OK

 ’

2.

 The display shows ‘

In

’ or ‘

Out

’ and the icon ‘ 

P

 

‘ flashes.

3.

 Press keys ‘   ‘ and ‘   ‘ to change the value (

In

: internal sensor -

 

Out

: remote sensor); 

each change is automatically stored in 

memory

.

4.

 To return to the list of user parameters, press the ‘

OK

’ button.

5.

 To exit the user parameter settings and resume normal operation, 

press the ‘   ‘ button or wait 10 seconds without pressing any key.

WARNING: When the regulation is set according to the remote 

sensor ‘ Out ‘ and in case this sensor is missing or broken, the 

temperature regulation will be performed according to the 

internal sensor, even if the parameter remains set on ‘ Out ‘.

CLE

’ SETTING CLEANING PROGRAM

This program is useful when the house is being cleaned and the 

windows are opened thus making both the heating and cooling of the 

premises unnecessary. In these conditions, the relays are blocked in 

Off for two hours.
Note: Access to the cleaning program is NOT allowed when the 

programmable thermostat is in ‘holiday mode’.
To activate the cleaning program, select the parameter ‘

CLE

’ and 

press the ’

OK

’ button: the display shows the ‘ 

 ‘ icon flashing and, 

in place of the clock, the time remaining before returning to normal 

operation is shown.

The device will go back to the previous operating mode after two 

hours or if you press the ‘

   

’ button again.

HOL

’ SET HOLIDAY PROGRAM

If you intend to be away for a relatively long period it is advisable 

to activate the Vacation Program, which will suspend the active 

operating mode for the desired number of hours (from 1 to 95) or 

Table 1

Note: the dew point, highlighted in the table, refers to the 

environmental conditions considered excellent in the summer:

 

Dew point = 16.3°C, with room temperature at 26.0°C and 

room humidity equal to 55.0%RH.

ATTENTION

- Condensate will form on the surfaces with temperature lower 

than or equal to that of the dew point calculated C-dP.

- The dew point is calculated automatically by the equipment when 

environmental conditions change.

For all details see ‘ ‘ C-dP ’ DEW POINT MANAGEMENT ‘.

Safety Control Algorithm

The ‘ Safety Control ‘ algorithm is used to manage the two relays 

controlling the thermostat and the programmable thermo-hygrostat.

The algorithm allows not to activate the two relays simultaneously, 

so as not to burden the electric line in the start-up phase (peak) of the 

temperature and humidity control systems.

Practically, the activation is manages in a way not to have overlapping 

on activation of the two commands.

SETTING THE USER PARAMETERS

To enter the mode for setting the programmable thermo-hygrostat 

parameters, proceed as follows:

1.

 Press the ‘   ‘ button; the display will show the ‘ 

P

 

‘ icon 

(bottom right) and the word ‘ 

PrOG

 ‘.

2.

 Press  the  ‘   ‘ button repeatedly to scroll through the user 

parameters:

  Schedule Programming 

‘ 

PrOG

 ’

  Antifreeze Setting 

‘ 

AFr

 ’

  Hysteresis Setting 

‘ 

HYS

 ’

  Optimization Function Setting 

‘ 

OPt

 ’

  Internal sensor Offset setting 

‘ 

OFS1

 ’

  Remote sensor Offset setting 

‘ 

OFS2

 ’

  Regulation sensor choice setting 

‘ 

rEG

 ’

  House hold program Setting 

‘ 

CLE

 ’

  Vacation program Setting 

‘ 

HOL

 ’ 

Setting heating or cooling 

‘ 

H-C

 ’

  Programmable thermo-hygrostat hysteresis setting 

‘ 

HYH

 ’

  Setting humidity sensor Offset 

‘ 

OFSH

 ’

  Setting Dehumidification or Humidification 

‘ 

dE-H

 ’

  Dew point control 

‘ 

C-dp

 ’

  Rate of check on dew point 

‘ 

Cndp

 ’

  Thermostat on time timer 

‘ 

Cntr

 ’

  Reset to default data 

‘ 

dFLt

 ’

3.

 Press the ‘

OK

’ button to modify the selected parameter; the ‘ 

P

 

‘ 

icon flashes.

4.

 Configure the data associated with each individual parameter as 

illustrated below.

5.

 To quit from the user parameters setting, press key ‘

   

’ or wait 10 

seconds wothout pressing any key.

‘ 

PrOG

 ‘: SCHEDULE PROGRAMMING

Usually the circular band of dashes in the display shows the operating 

mode (Comfort, Economy, Off / antifrost) of the thermostat, while 

the vertical strip on the left shows the current day of the week 

(1=Monday .. 7=Sunday) high lighted with a square around the 

number to which it relates programming.

To facilitate the programming operation it is sufficient to remember 

this rule:

Economy mode:

one dash lit (internal).

Comfort mode:

two dashes lit.

Off/Antifreeze mode:

no dashes lit.

Days of the week:

1 Monday .. 7 Sunday.

The  box  indicates  the 

current day or group of days.

To set the program schedule proceed as described below:

Note: You will exit the programming mode without memorizing 

the programmed schedule if more than 10 seconds elapse 

and you do not press any button; or else you can confirm 

the settings in sequence by pressing the ‘OK’ button 

without making any changes.

1.

 Select parameter ‘ 

PrOG

 ’ and press button ‘ 

OK

 ’: the display 

shows the word ‘ 

dAy

 ’, icon ‘ 

P

 

‘ and the  square symbols 

corresponding to the current day or group of flashes.

2.

 Press buttons ‘   ’ and ‘   ’ to set the combination of days to be 

Summary of Contents for T.HYGROS THW02B

Page 1: ...highlighted by a box surrounding the number corresponding to the day of the week 1 Monday 7 Sunday 8 Confirm by pressing OK the output of the time and day setting is automatic Time Temperature Humidity Display By repeatedly pressing the the display can alternately show the actual time the room temperature in C read by the internal sensor distinguished by the icon the room temperature in C read by ...

Page 2: ... OK button 5 To exit the user parameter settings and resume normal operation press the button or wait 10 seconds without pressing any key OFS2 REMOTE SENSOR OFFSET SETTING With this parameter it is possible to correct the temperature reading of the remote sensor by 5 C in order to correct any systematic reading errors due to the positioning of the remote sensor in areas unsuitable for measuring th...

Page 3: ...cation devices on the basis of the comparison of the temperature value of the dew point calculated and the temperature values relative to the dew points set in the sub parameters TF1 and TF2 The following graphics describe the dew point control mode HYdP hysteresis OFF PRIORITY ON THERMOSTAT cooler dehumidifier TF1 0 C HYdP hysteresis PRIORITY ON DEHUMIDI FIER dP TF2 ON TF1 HYdP Dove dP dew point ...

Page 4: ...pleted and must be replaced In this case both the relays are placed in the safety position N C and the display alternately shows the time or temperature or humidity and the word BATT If the batteries are not replaced as soon as possible the or symbols will also flash indicating that the device is blocked To replace the batteries proceed as follows 1 Open the flap of the battery compartment Fig 1 2...

Page 5: ...at to the wall plate using the supplied screw that is located inside the battery compartment Fig 8 5 Fig 8 Insert the batteries in the battery compartment I in Fig 1 see paragraph HOW TO INSERT REPLACE THE BATTERIES 6 QUICKGUIDEFORSETTINGTHETIMESCHEDULE Press button P The display shows PrOG with the icon P turned on Press key OK the display shows the word dAY the icon P and the squares correspondi...

Reviews: