background image

- ENGLISH -

THW01B0000SE 031861 190319

5

INSTALLATION

 

      WARNING

- To adjust properly room temperature, install the thermostat 

far from heat sources, airstreams or particularly cold walls 

(thermal bridges).

- In order to grant the electrical safety, it is mandatory to 

screw the programmable thermo-hygrostat body to the wall 

mount plate through the two screws supplied which must be 

mounted in the battery holder.

- If the load controlled by the relay of the programmable 

thermo-hygrostat operates with mains voltage, the 

connection must be made via an omnipolar switch complying 

with current standards and with a contact opening of at least 

3 mm in each pole.

- Installation and electrical wirings of this appliance must be 

made  by  qualified  technicians  and  in  compliance  with  the 

current standards.

- Before wiring the appliance be sure to turn the mains power off.

The device is designed to be installed in a standard recess (or wall) 

mounted junction box with two or three modules or else directly on 

the wall using the screw anchors provided.
To install the device carry out the following steps:

Release  the  wall  mount  plate  fitted  under  the  base  of  the 

programmable thermo-hygrostat as shown in Fig. 2.

Fig. 2

1

2

1

Fix the plate directly on the wall or onto 2 or 3 module junction 

boxes by means of the two holes for screws (distance between 

centres: 60 mm or 85mm), taking care to pass the wires 

through the opening as shown in Fig. 3.

2

Fig. 3

Move the thermostat to the wall plate by fitting first the teeth 

of the base with the relevant holes of the plate and then exert 

a pressure on the device to the left side until the plastic teeth 

of the plate snap.

4

2

1

Fig. 7

Secure the bodyof the programmable thermostat to the wall 

plate using the supplied screw that is located inside the battery 

compartment (Fig.8).

5

Fig. 8

Insert the batteries in the battery compartment (

I

 in Fig. 1); 

see paragraph ‘ HOW TO INSERT/REPLACE THE BATTERIES ’.

6

QUICK GUIDE FOR SETTING THE TIME SCHEDULE

• 

Press button ‘ 

’.

• 

The display shows ‘ 

PrOG 

’ with the icon ‘ 

P

 

‘ turned on.

• 

Press key ‘ 

OK 

’: the display shows the word ‘ 

dAY

  ’,  the  icon           

‘ 

P

 

‘ and the squares corresponding to the flashing days.

• 

Press buttons ‘   ‘ and ‘   ‘ in order to choose one of the four 
days combinations available as pre-set.

• 

Press button ‘ 

OK 

’ to confirm the choice.

• 

The display shows hour 00:00 with the relevant dash, in the upside 

right, flashing.

• 

Press one of the following buttons to select the temperature 
regulation level desired:

 

Comfort mode

Press the ‘ 

 ‘ button.

 

Off / Antifreeze

Press the ‘   ‘ button.

 

Economy mode

Press the ‘   ‘ button.

 

Moving the time cursor

:  Press button ‘   ’ or ‘   ‘.

  Each time the button which sets the regulation mode is depressed, 

the time cursor automatically jumps into the next half hour.

• 

Once the time schedule for the day or group of days selected has 
been set, press button ‘ 

OK 

’.

The display will show the time schedule for the next day or group 

of days until the whole week has been covered.

• 

Once the time schedule for the whole week has been set, press 
button ‘ 

OK 

’. The programmable thermo-hygrostat will store the 

program into its memory and the word ‘ 

MEMO 

’ is shown on the 

display, then it will automatically quit the time schedule setting 
procedure.

Connect the remote sensor (if present) or the phone interface 

to connector ‘

C

’ shown in Fig. 6. The load for the thermostat 

section must be wired to the terminal block ‘

A

’ shown in Fig. 6, 

meanwhile the load for the hygrostat section must be wired to 

the terminal block ‘

B

’ shown in Fig. 6.

Fig. 6

A

C

B

Make electrical wirings by passing the wires through the 

rectangular opening in the wall plate (Fig. 3), and according to 

the diagram in Fig. 4 or Fig. 5.

3

Fig. 4

Fig. 5

WHITE

TELEPHONE 

INTERFCE

RED

BLACK

TO THE BOILER / COOLER

HYGROSTAT 

RELAY

THERMOSTAT 

RELAY

TO THE DEHUMIDIFIER / HUMIDIFIER

WHITE

TELEPHONE 

INTERFACE

REMOTE SENSOR 

FOR DEW POINT 

CONTROL OR COMFORT 

REGULATION

RED

BLACK

LOAD

LOAD

HYGROSTAT 

RELAY

THERMOSTAT 

RELAY

REMOTE SENSOR FOR DEW POINT 

CONTROL OR COMFORT REGULATION

Summary of Contents for T.HYGROS THW01B

Page 1: ...ighlighted by a box surrounding the number corresponding to the day of the week 1 Monday 7 Sunday 8 Confirm by pressing OK the output of the time and day setting is automatic Time Temperature Humidity Display By repeatedly pressing the the display can alternately show the actual time the room temperature in C read by the internal sensor distinguished by the icon the room temperature in C read by t...

Page 2: ... button 5 To exit the user parameter settings and resume normal operation press the button or wait 10 seconds without pressing any key OFS2 REMOTE SENSOR OFFSET SETTING With this parameter it is possible to correct the temperature reading of the remote sensor by 5 C in order to correct any systematic reading errors due to the positioning of the remote sensor in areas unsuitable for measuring the r...

Page 3: ... del punto di rugiada impostato nel sottoparametro d EC HYdP dew point hysteresis equal to 0 5 C cannot be modified d FP dew point control on fixed points If the dew point control function C dP is activated on d FP the programmable thermo hygrostat controls the cooling and dehumidification devices on the basis of the comparison of the temperature value of the dew point calculated and the temperatu...

Page 4: ... are lit inside the symbol If the symbol completely empty flashes it means that the batteries are depleted and must be replaced In this case both the relays are placed in the safety position N C and the display alternately shows the time or temperature or humidity and the word BATT If the batteries are not replaced as soon as possible the or symbols will also flash indicating that the device is bl...

Page 5: ...n Fig 1 see paragraph HOW TO INSERT REPLACE THE BATTERIES 6 QUICKGUIDEFORSETTINGTHETIMESCHEDULE Press button P The display shows PrOG with the icon P turned on Press key OK the display shows the word dAY the icon P and the squares corresponding to the flashing days Press buttons and in order to choose one of the four days combinations available as pre set Press button OK to confirm the choice The ...