13. Trouble shooting

Failure

Reason

Troubleshooting

 Unit
doesn't
start

 No power supply

 Check the electrical connection

 Cabinet temperature is lower
 than set point

 Wait until the set point is reached. The unit will  then
 start automatically. If the set point of the cabinet
 temperature  is too high, reduce it accordingly.

 Door contact is open

 Close the cabinet door or bridge the door contact.

Unit
doesn't
cool

 Compressor is faulty

 Please get in contact with one of our service
 partners.

 The circuit breaker of the
 compressor got activated

 Check the cooling capacity. In case the
 cooling capacity is too small, install the unit
 at a different place or add another cooling unit. 

 The evaporator and / or
 condenser are extremely dirty.

 Evaporator and /or condenser need cleaning

Evaporator
is iced up

 Not enough refrigerant due to
 leaking cooling circuit

 Refill refrigerant and re-seal cooling circuit.
 Please contact the manufacturer.

 Ambient temperature is much
 lower than the stated operating
 temperature range

 Install the unit at a different place. The ambient
 temperature must be within the stated operating
 temperature range.

 The control cabinet is
 not sealed properly.

 The control cabinet needs re-sealing.

 Fan or fan capacitor on
 the cold side are faulty

 Replace fan and/or fan capacitor.

Too much
condensate 

 Cabinet door not closed

 Ensure that cabinet door is closed properly

 The cabinet is not
 sealed properly

 The control cabinet needs re-sealing.

 Incomplete gasket between
 cooling unit and cabinet 

 Please check gasket

Uneven air circulation
inside the cabinet

 Cabinet air intake and air
 outlet are blocked 

 Ensure that both are unblocked and that air
 can circulate

 Cabinet volume too big for
 this cooling unit

 Check the cooling capacity. In case the cooling
 capacity is too small, install the unit at a different
 place or add another cooling unit. 

Condenser fan
doesn't work

 Fan is faulty

 Replace fan

Evaporator fan
doesn't work

 Fan is faulty

 Replace fan

Note: Before you contact one of our service partners please press the test button of the
controller. Like this the fans and the evaporator are getting switched on independent of the internal
cabinet temperature. In cases of emergency you can contact us under one of the tel. numbers stated
on the last page.

14. Maintenance & Cleaning

The cooling unit is generally maintenance free and can be operated without filters in most
environments. For units with filters these should be checked, cleaned and if necessary replaced on a
regular basis. In addition the unit should have regular functional tests (approx. every 2,000 hours
depending on the grade of ambient pollution).

15. Maintenance

 

Summary of Contents for KG 2025-24V

Page 1: ...y instructions 3 4 Technical information 4 5 Functional principle 4 6 Technical data 5 8 Mounting 6 9 Electrical connection 7 10 Controller Layout Description 11 11 Wiring diagram 12 12 Taking into op...

Page 2: ...e instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a specific pictogram such as one of the following High electric voltage Indicate...

Page 3: ...ds to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid safety regulati...

Page 4: ...blems in extreme ambient conditions e g dusty and oily air The operating temperature range is between 20 C and 55 C Units can be ordered with an additional electrical cabinet heater For the cooling ca...

Page 5: ...psig Temperature range 10 C 55 C Air volume flow Ambient air circuit 315 m h Cabinet air circuit 190 m h Mounting Internal External Housing Material Mild steel powder coated Dimension HxWxD 310 x 475...

Page 6: ...Sealing To guarantee that the unit works perfectly ensure that the control cabinet is completely sealed to min IP54 according to EN 60529 a good seal exists between the control cabinet and the unit if...

Page 7: ...oute the pipe to a drain or a collector 9 Electrical connection High electric voltage present Installation maintenance cleaning and any other work must be carried out by qualified personnel only The p...

Page 8: ...Contacts P1 P2 P3 are potential free and require an external power source if wired to operate external components indicator lamps switches The load on these contacts is not to exceed 30V DC 4 A or 12...

Page 9: ...oor closed CF LED Controller Function blinks when controller is running Fault warning connection The fault warning is connected via terminals P1 P2 P3 on the connection terminal block The temp adjustm...

Page 10: ...m signal must be at least 5 C higher than the setting for the cabinet s internal temperature Close the unit as prescribed Check that the new setting meets requirments and if not repeat the above proce...

Page 11: ...PS Optional powered sensor SDP Simple display port ITS Internal temperature sensor AO Alarm output UART UART RS485 RS485 CD Compressor data DC Door contact IFO1 Internal fan out 1 IFO2 Internal fan ou...

Page 12: ...tional AO Alarm output CD Compressor data DS Door switch F Fuse 16 A T PI DC Power M1 Internal fan M2 Internal fan M3 Ambient fan M4 Ambient fan M5 Compressor CC Compressor controller TS1 Comp thermal...

Page 13: ...Version Nr 1 1 20 06 2017 Doc Nr 9920250241 13 16...

Page 14: ...ading taken by the sensor in such a way to operate in the most efficient manner and to reduce the switching on and off of the compressor This helps to keep the temperature inside the control cabinet a...

Page 15: ...re sealing Fan or fan capacitor on the cold side are faulty Replace fan and or fan capacitor Too much condensate Cabinet door not closed Ensure that cabinet door is closed properly The cabinet is not...

Page 16: ...ton box containing the unit must be examined for signs of transport damage Any transport damage to the carton box could indicate that the unit itself has been damaged in transit which in the worst cas...

Reviews: