16. Taking into operation

Attention!
The unit can be damaged by lack of lubricant. To ensure that the compressor is adequately lubricated the oil,
which has been displaced during transport, must be allowed to flow back into it. The unit must therefore be
allowed to stand for at least 30 min. before being connected to the mains and taken into operation.

The unit / system must be protected with a MCB Type D or K. Upon connection the internal fan will start
working. If the temperature inside the enclosure is higher than the set value of the controller both the
compressor and external air fan start working. The cooling cycle will either stop once the air inside the
enclosure reaches the set temperature minus hysteresis or once the minimum On-time is reached. The setpoint
for the internal enclosure temperature is pre-set at 95°F.

The hysteresis is 3K, the minimum ON-time is 4 minutes, the minimum OFF-time is 3 minutes, for units with a
cooling capacity of more than 1 kW is it usually 7 minutes.

17. Trouble shooting

Failure

Condition

Cause

Solution

 Unit
 doesn't
 cool

 Internal fan does not work

 Power not connected.

 Verify power supply

 Internal fan works, external fan
 and compressor don't work

 Enclosure temperature is below
 setting temperature (St)

 Verify values of parameter
 "St"

Door switch contact is open

 Verify door switch

Controller doesn't work

 Replace controller

 Internal fan works, external fan
 and  compressor don't work.
 Display shows alternating OFF 
 and temperature

 The sequence of the phases
 inside the power supply
 connector is incorrect

 Change phases inside power 
 supply connector

 Unit
 doesn't
 cool

 External and internal fan work,
 compressor does not work

 Compressor motor electrical
 failure

 Have compressor replaced  
 by qualified service technician

 Capacitor for compressor failed  Replace capacitor

 Compressor works, external fan
 doesn't work

 External fan needs to be
 replaced

 Replace external fan

 Enclosure
 temperature 
 too hot

 Compressor and fans (external
 and internal) work all the time

 Cooling unit undersized

 Enclosure needs a cooling
 unit with with higher capacity

 Compressor and external fan 
 work in alternating mode
(ON / OFF)

 Thermal compressor protector
 triggered 

 Verify if ambient temperature
 is too high,clean condenser

 Refrigerant leakage

Contact dealer/service center

 Excessive 
 condensate

 Enclosure door open

 Ambient air gets into the  
 enclosure

 Ensure door is closed, add
 a door  switch and connect
 it to controller

 Enclosure door closed

 Enclosure IP protection class 
 is  below IP54

 Seal all openings of the
 enclosure

 Damaged or misplaced sealing
 strip

 Repair sealing strip
 accordingly

Summary of Contents for 87061082USL

Page 1: ...ple 5 6 Technical data 6 7 Performance graph 7 8 Mounting 8 9 Condensate management 9 10 Mounting Principle 10 11 Cut out dimensions 11 12 Dimensions H x W x D 12 13 Electrical connection 13 14 Contro...

Page 2: ...instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage Indicates...

Page 3: ...ad with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid sa...

Page 4: ...separate air circuits which ensure that the clean cabinet air does not come into contact with the ambient air which may well be dirty or polluted Enclosure cooling units can dissipate large quantities...

Page 5: ...nt thus taking it to high pressure and high temperature and pushes it through the condenser where it is cooled by ambient air thus passing from the gas to the liquid state At the liquid state it then...

Page 6: ...mpeded Ambient 140 240 cfm Cabinet 70 105 cfm Mounting Wall mounted Housing Material Stainless steel AISI 304 V2A Dimension H x W x D 15 x 9 85 x 9 85 inch Weight 35 lbs Voltage Frequency 120 V 50 60...

Page 7: ...Version Nr 1 5 25 07 2022 Doc No 9987061082USL 7 22 7 Performance graph...

Page 8: ...e cut packaging opening facing up STEP 2 Pull o the packaging opening STEP 3 Hang the transport loop of the unit in the transport hook and lift it slightly STEP 4 Pull o the packaging and slide out th...

Page 9: ...by storage conditions please check this template by verifying values of the largest dimensions before drilling Fit the sealing strip on the cooling unit on the side connected to the enclosure and fol...

Page 10: ...within the rst 15 minutes after installation Use only the supplied mounting hardware Tighten Screws to 4 5 Nm Ensure the mounting surface does not warp after assembly and reinforce it if necessary 1 M...

Page 11: ...Version Nr 1 5 25 07 2022 Doc No 9987061082USL 11 22 11 Cut out dimensions...

Page 12: ...Version Nr 1 5 25 07 2022 Doc No 9987061082USL 12 22 12 Dimensions H x W x D...

Page 13: ...if closed Door contact terminals bridged or NC door switch connected contact must be closed when cabinet door is closed c68 1 ON if open Remove bridge or NO door switch connected contact must be open...

Page 14: ...ress 2 Alarm relay active 3 Heater relay active 4 Ambient blower relay active Alarm Flashes when alarms are active Heating mode Signals operation of unit in heating mode Cooling mode Signals operation...

Page 15: ...e C 0 F 1 P25 for low temperature alarm threshold default 10 C 14 F P26 for high temperature alarm threshold default 55 C 131 F c68 for door contact NO NC logic change 0 ON if closed 1 ON if open Cont...

Page 16: ...with an icon ashing triangle alternating with the standard display If more than one error occurs these are shown in sequence on the display Failure Code Description Solution OFF Door open Close the en...

Page 17: ...button for at least 5 seconds When pressing PRG for 3 seconds the rmware revision code is displayed for 2 seconds When cleaning the controller panel do not use ethanol hydrocarbons ammonia or their by...

Page 18: ...Version Nr 1 5 25 07 2022 Doc No 9987061082USL 18 22 15 Wiring diagram Power Cable AWG18 BK L1 BU N GNYE PE Signals Cable AWG20 GY Alarm NC BN Alarm COM BU Alarm NO RD Door contact PK Door contact...

Page 19: ...sor don t work Enclosure temperature is below setting temperature St Verify values of parameter St Door switch contact is open Verify door switch Controller doesn t work Replace controller Internal fa...

Page 20: ...d be replaced immediately Do not use a steam jet or high pressure to clean the lter mats Do not wring out the lter mats If the ambient air is extremely oily we recommend the use of metal lters see acc...

Page 21: ...temperature range 40 F to 158 F relative humidity at 77 F max 95 the air conditioner should always be stored according to the installation position Returning the unit To avoid transport damage the un...

Page 22: ...s supplied Spare parts Accessories Description QTY Image Instruction manual 1 CE Declaration 1 Mounting template 1 M6 16 bolts 6 A6 4 toothed washers 6 A6 4 washers 6 Seifert Systems Inc 75 Circuit Dr...

Reviews: