The solenoid valve is switched electrically. If the unit power is off, the valve switches to open.
5. Units with temperature controller
The unit is equipped with a temperature controller which regulates the function of the unit. On normal working
conditions the display shows the temperature inside the enclosure. The controller “set point” for the interior of
the enclosure (parameter St / St1) is pre-set at 35°C and can be adjusted b20°C and +50°C.
The High temperature alarm (parameter AH) is preset at 55°C. The High Temperature Alarm relay is delivered
as “normally closed” (H1=1). If you need to change it to “normally open”, please modify value of parameter H1
(H1=2).

Modifying controller parameters
1. Press the SET button for more than 3 sec. (if there are active alarms, mute the buzzer).The display shows the
parameter code ‘PS’ (password).
2. Only for parameters requiring password: Press the SET button to access the password setting, use the UP and
DOWN buttons to scroll the numbers until displaying, “22” (default password to access the parameters), press
the SET button to confirm the password
3. Use the UP and DOWN buttons to scroll the parameters. The LED corresponding to the category of
parameters will be on
4. Press SET to display the value associated with the parameter
5. Increase or decrease the value using the UP or DOWN button respectively
6. Press SET to temporarily save the new value
7. Press the SET button for more than 3 sec. to permanently save the new parameters and exit the parameter
setting procedure.

If no button is pressed for 60 sec. all changes made to the parameters, temporarily saved in the RAM, will be
cancelled and the previous settings restored. The cooling unit manufacturer is in no way liable for any
alterations the customer may make to the factory set parameters, unless the manufacturer has authorized the
customer in writing to change them.

This manual is intended as quick reference for controller, for a full controller manual or if you need to restore
the factory parameters please go to our website to download the full manual or to locate your nearest servicing
office.

6. Units with door switch
The unit can be switched on and of via a door contact switch (optional). When delivered the door contact
terminals are bridged on the female connector. To connect the door contact switch remove the bridge and
connect door contact switch. The contact must be closed when the cabinet door is closed.

11. Maintenance & Cleaning

The unit should have regular functional tests (approx. every 2,000 hours depending on the grade of ambient
pollution).

12. Maintenance

Every unit is given a performance test under load at the factory. The units are largely maintenance-free,
however, the following points should be observed:

1. Fan replacement
Before replacing the fan, the equipment must be switched off from the power supply (pull out mains plug or
connecting cable). The rated life time of the fan is L10 = 30.000 hours under normal operational conditions.
Should it become necessary to replace the fan, remove the support for the fan by loosening the 4 fastening
screws (RK-2114 models only). To detach the fan from the fan support loosen a further 4 screws and the fan
connecting cable.
When connecting the new fan, take care that the correct polarity is maintained.

Summary of Contents for 2300110

Page 1: ...l Regulations 2 3 Safety Instructions 3 4 Settings 4 5 Functional Principle 5 6 Technical Data 6 7 Mounting 7 8 Mounting Principle 9 9 Wiring Diagram 10 10 Taking into Operation 11 11 Maintenance Clea...

Page 2: ...ns in the instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage I...

Page 3: ...with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid safe...

Page 4: ...55 P The cooling water used must be soft enough to avoid scale deposits but should not be too soft as this would corrode the heat exchanger Where the cooling water is cooled for reuse part of the wate...

Page 5: ...s constantly providing continuous circulation of the air in the cabinet This circulation prevents hot spots within the control cabinet During this process the coolant heats up and is returned to the c...

Page 6: ...peded 85 240 m h Mounting Wall mounted recessed Housing Material Mild steel powder coated Dimension A x B x C D E 303 x 153 x 84 mm Weight 4 5 kg Voltage Frequency 120 V 60 Hz Starting Current 0 74 A...

Page 7: ...g template enables the unit to be installed quickly For mounting the template should be attached to the wall of the cabinet and the holes for the xing screws should be drilled in the wall of the cabin...

Page 8: ...ion drain pipe should be attached as required e g in conditions of high humidity To install an oel cleaning drain 2 pipe please follow below steps Remove the plastic stopper from in the base of the un...

Page 9: ...Version No 1 4 02 06 2021 Doc No 992300110 9 13 8 Mounting Principle 1 Bolt 2 Toothed washer 3 Washer 4 Enclosure 5 Mounting gasket...

Page 10: ...Version No 1 4 02 06 2021 Doc No 992300110 10 13 9 Wiring Diagram M1 Radial fan X3 3 pin connector L1 Live N Neutral PE Earth protection...

Page 11: ...the unit To set the ow rate Q turn the thermostatic head Set the indicator position to the required cabinet temperature The work s setting of the water ow regulator is 35 C The adjustment range is 20...

Page 12: ...ure If no button is pressed for 60 sec all changes made to the parameters temporarily saved in the RAM will be cancelled and the previous settings restored The cooling unit manufacturer is in no way l...

Page 13: ...ned in the original packing or in a packing case and must be strapped to a pallet If the unit cannot be returned in the original packing please ensure that A space of at least 30 mm must be maintained...

Reviews: