TB XRN2 02.00 E
33
8.3
Setting ranges and steps
Function
Para-
meter
Setting range
Steps
Tolerance
U</<<
U</<<
t
U<
t
U<<
U
N
= 100 V:
2...200 V (EXIT)
U
N
= 230 V:
2...460 V (EXIT)
U
N
= 400 V:
4...800 V (EXIT)
0.04...50 s (EXIT)
1 V
1 V
2 V
0.01; 0.02; 0.05; 0.1;
0.2; 0.5; 1.0; 2.0 s
±
1% of set value
or <0.3% U
N
±
1% or
±
15 ms
U>/>>
U>/>>
t
U>
t
U>>
U
N
= 100 V:
2...200 V (EXIT)
U
N
= 230 V:
2...460 V (EXIT)
U
N
= 400 V:
4...800 V (EXIT)
0.04...50 s (EXIT)
1 V
1 V
2 V
0.01; 0.02; 0.05; 0.1;
0.2; 0.5; 1.0; 2.0 s
±
1% of set value
or <0.3% U
N
±
1% or
±
15 ms
Rated frequency
f
N
f = 50 Hz / f = 60 Hz
Frequency
measuring repeti-
tion
T
2...99 (Cycles)
1
Frequency
element 1 - 3
f
1
-
f
3
t
f1
-
t
f3
30...49.99; EXIT; 50.01...70 Hz
1
40...59.99; EXIT; 60.01...80 Hz
2
t
f,min
3
...50 s; EXIT
0.1; 0.01 Hz
0.01; 0.02; 0.05; 0.1;
0.2; 0.5; 1.0; 2.0 s
0.005 Hz
±
1% or
±
20 ms
df/dt-Step
df/dt-Measuring
repetition
df
dt
0.2...10 Hz/s (EXIT)
2...64 Periods
0.1; 0.2; 0.5 Hz/s
1
0.1 Hz/s
∆Θ
∆Θ
2°...22° (EXIT)
1°
±
1°
Vector surge
logic
1/3
1Ph / 3Ph
Voltage theshold
for frequency
measuring
U
B
<
(LED 'f'+
∆Θ
/df)
U
N
= 100 V:
5...100 V
U
N
= 230 V:
12...230 V
U
N
= 400 V:
20...400 V
1 V
1 V
2 V
±
1% of set value
or <0.3% U
N
Serial Interface
RS
1 - 32
1
Table 7.1: Setting ranges and steps
1
At 50 Hz rated frequency
2
At 60 Hz rated frequency
3
t
f,min
min. time delay; t
f,min
= (T+1)
⋅
20 ms
Summary of Contents for XRN2
Page 1: ...XRN2 Mains decoupling relay ...
Page 40: ...40 TB XRN2 02 00 E ...