7.15
Ipeak> – Peak-Value Overcurrent
7.15.1
Ipeak>: Device Planning Parameters
Ipeak> . Mode
[Device planning / Projected Elements]
use
“-”, use
P.1
Peak-Value Overcurrent, general operation mode
Ipeak> . Definition
[Device planning / Definition]
Trip
Trip, Alarm
P.1
Peak-Value Overcurrent: If set to “Alarm”: The function operates as a supervision function, i.e. a fault generates
neither alarm nor trip, but an »Alarm« signal gets issued instead. If set to “Trip”: The function operates as a
protection function, i.e. trips the breaker in case of a fault.
7.15.2
Ipeak>: Settings
Ipeak> . Function
[Protection Para / Ipeak>]
Active
Inactive, Active
P.1
Permanent activation or deactivation of module/stage.
Ipeak> . I
[Protection Para / Ipeak>]
8.0In
4.0In . . . 20.00In
P.1
Pickup threshold, defined as RMS value (i.e. peak current value divided by √2). If the pickup value is exceeded, the
module/element starts to time out to trip.
Ipeak> . t
[Protection Para / Ipeak>]
0.0s
0.00s . . . 5.00s
P.1
Time delay for trip or alarm
Ipeak> . ExBlo
[Protection Para / Ipeak>]
“-”
“-” . . . Prot . Pos OFF
P.1
External blocking of the module if the state of the assigned signal is true.
62
WIC1
WIC1-1.0-EN-REF
7 Protection Parameter
7.15 Ipeak> – Peak-Value Overcurrent