If there are two of the same air
conditioners installed, they cannot be
controlled separately. When you operate
either remote, it will turn on both air
conditioners if they are both within signal
range (6 metres).
Don’t let the remote control drop onto
hard surfaces or be subjected to sudden
shocks in any way. The warranty does not
cover misuse or accidental damage.
Don’t place the remote control in direct
sunlight, or near extremes of temperature.
This will affect the control’s temperature
reading.
Don’t allow the remote control to get wet.
Don’t place near strong electromagnetic
waves.
Don’t mix old and new batteries ! If the
remote control will not be used for a long
time, remove the batteries to avoid
corrosion.
Care of your remote control
Preparation before operation
During Operation
Remove the battery cover and insert new
batteries
.
Remove the batteries and replace with new
ones. If this does not solve the problem
contact your nearest service centre for
advice.
(AAA), making sure the + and - are
matching the compartment markings (Fig
10)
If the remote control will not operate the air
conditioner, the batteries may need to be
replaced.
The air conditioner must be plugged in
and switched on for the remote control to
operate the air conditioner. To use, point at
the signal receiving window on the front
panel and press the remote button. The air
conditioner will “beep” when a signal has
been received. If there is no beep, press the
remote button again, ensuring it is within
range (6 metres) of the air conditioner.
Note!
!
NOTE:
WASTE BATTERIES SHOULD
BE DISPOSED OF CORRECTLY
REMOTE CONTROL
6
®
9
Signal
transmission point
Temperature
adjust buttons
Ion / TiO button
2
(only active for
models CM12WX
and CM15WX)
Sleep mode button
Fan speed
adjust buttons
Mode buttons
(Cool-Dehumidify-
Fan-Heat)
Timer on / adjust
button
Power ON / OFF
button
Battery
compartment
Battery cover
10
ClimateMaster series Portable Refrigerated Air Conditioner
Starting the air conditioner
Step 1:
Ensure the cooler is plugged in
and switched on.
Step 2:
Step 3:
Cooling mode
Dehumidifying mode
Fan mode
Heat mode -
Step 4:
!
Step 5:
Press the ON/OFF button on the
remote control or ON/OFF button on the
control panel to start the air conditioner.
Press the MODE button
on
the control panel or remote control to
select the desired operating mode (Fig 7 &
11):
- refrigerated
cooling (all models)
- for
extracting moisture from the air
- Fan only operation
(no cooling)
reverse cycle
heating (CP12HS, CP15HS and
CM15HW only)
Press
/
on the control panel
or on the remote control to select the
desired operating ‘set’ temperature.
In Cooling mode, cooling will occur if the
set temperature is less than the room
temperature.
In Heating mode, heating will occur if the
set temperature is greater than the room
temperature.
Do not set the cooling temperature
too low. This will consume more power.
24°C is the recommended set
temperature, with high fan speed.
Changing the set temperature will
have no effect in DEHUMIDIFYING or FAN
modes.
Press the FAN SPEED button
on the control panel or remote control to
adjust the fan speed. Each press will
cycle the fan speed through low, medium
& high.
r s
The set temperature range is 16°C-31°C
Tip
Note!
Step.2
Step.8
Step.3
Step.5
Step.4
Step.7
Step.6
OPERATION
11
Note!
Important!
the fan speed is automatically set to
low in dehumidifying and sleep modes.
In Cooling & Heating modes, the fan will
continue to run even when the compressor
has cycled off.
During heating mode the unit
may enter a defrost cycle. When this
occurs, the compressor will stop and the fan
will continue to run. This is a normal
function for all reverse cycle air conditioners.
The compressor will re-start and normal
heating operation will recommence when
the defrost cycle is complete.
During cooling and heating mode, water will
collect in the air conditioner’s tank. In
cooling mode this water is recirculated and
some will be exhausted out with the hot air,
but will slowly fill up the tank. This occurs
more quickly in humid conditions. There is
no recirculation in heating mode. If the tank
should fill, the ‘water full’
symbol will
flash on the control display, the unit will
‘beep’ 15 times and then shut down. The
cooler cannot be restarted until the water
tank is drained. Refer to the Maintenance
section for draining the tank should this
occur.
SEELEY INTERNATIONAL
–
OWNER’S MANUAL
7