Secutron MR-2312-AT Installation Manual Download Page 7

MR-2312-AT Remote Annunciator Wiring and Instruction Manual

3

Wiring Instructions

The RS-485 Wiring to the MR-2312-
AT Module is recommended to be 
twisted shielded pair as shown in 
the diagram. The wire gauge may 
be:

• 22 AWG up to 2000 ft.

• 20 AWG up to 4000 ft.

The RS-485 wiring from the fire 
alarm control panel to the 
annunciator(s) must be point-to-
point from the fire alarm panel to the 
first annunciator, then to the next 
annunciator, and so on. No star 
wiring or T-tapping is allowed. Each 
MR-2312-AT Annunciator Module 
has a 120 ohm end-of-line resistor 
on its RS-485 output terminals. This 
is removed on all except the last 
wired module.

The 24 VDC field wiring needs to be of an appropriate gauge for the number of annunciators and the 
total wiring run length. Use the 

Current Drain for Battery Calculations

 on page 5 to calculate the 

maximum current for all annunciators summed together.

Note:

 All circuits are power limited and must use type FPL, FPLR, or FPLP power limited 

cable.

WARNING: 

Accidentally connecting any of the 24 VDC wires to the RS-485 wiring 

will 

result in damage

 to the annunciator and/or to the fire alarm control panel to which it is 

connected.

Total 

Maximum 

Current for all 

Annunciators

Maximum Wiring Run to Last Annunciator

Max Loop 

Resistance

18AWG

16AWG

14AWG

12AWG

0hms

Amperes

ft.

m

ft.

m

ft.

m

ft.

m

Ohms

0.12

1180

360

1850

567

3000

915

4250

1296

15

0.30

470

143

750

229

1200

366

1900

579

6

0.60

235

71

375

114

600

183

850

259

3

0.90

156

47

250

76

400

122

570

174

2

1.20

118

36

185

56

300

91

425

129

1.5

1.50

94

29

150

46

240

73

343

105

1.2

1.70

78

24

125

38

200

61

285

87

1.0

+

24 VDC
OUTPUT

-

S

S

-

+

-

+

-

+

RS-485
OUTPUT

RS-485
INPUT

24 VDC
INPUT

24 VDC POWER FROM FIRE ALARM CONTROL
PANEL OR PREVIOUS ANNUNCIATOR

24 VDC POWER TO
NEXT ANNUNCIATOR

RS-485 TO NEXT ANNUNCIATOR
(TWISTED SHIELDED PAIR)

RS-485 FROM FIRE ALARM OR PREVIOUS
ANNUNCIATOR (TWISTED SHIELDED PAIR)

Summary of Contents for MR-2312-AT

Page 1: ...58SEC WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be read...

Page 2: ......

Page 3: ...s and Displays 2 Wiring Instructions 3 DIP Switch Settings 4 Jumper Selection 4 Specifications and Features 5 Enclosure 5 Electrical Specifications 5 Current Drain for Battery Calculations 5 Warranty...

Page 4: ......

Page 5: ...by a keyswitch Each circuit indicator is a bi colour LED that is automatically configured to match the fire alarm control panel configuration Technical Support For all technical support inquiries plea...

Page 6: ...s Indicating and relay circuits are not remotely displayed For more details refer to the manual of the fire alarm control panel that the annunciator will be connected to The MR 2312 AT has a keyswitch...

Page 7: ...imum current for all annunciators summed together Note All circuits are power limited and must use type FPL FPLR or FPLP power limited cable WARNING Accidentally connecting any of the 24 VDC wires to...

Page 8: ...Jumper JP1 connects pins 2 and 3 and thus provides an eight bit checksum JW4 Jumper Intact Buzzer silence Lamp Test local function only System Reset Signal Silence are disabled Cut Jumper to have all...

Page 9: ...to 16 points Not expandable Standby 35 mA Max All LED s illuminated 140 mA max Current Drain for Battery Calculations The lamp test feature draws the maximum normal current because it illuminates all...

Page 10: ...installed correctly If a device operates only by AC power any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length are often ac...

Page 11: ...rted or awakened Audible notification appliances may be interfered with by other noise sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notifi...

Page 12: ...beyond the control of Secutron Inc such as excessive voltage mechanical shock or water damage damage caused by unauthorized attachment alterations modifications or foreign objects damage caused by per...

Page 13: ...e which Secutron Inc has predetermined and which may be revised from time to time will be charged for each unit repaired Products which Secutron Inc determines not to be repairable will be replaced by...

Page 14: ...Warranty Warning Information 10...

Page 15: ...MR 2312 AT Remote Annunciator Wiring and Instruction Manual 11...

Page 16: ...Cheektowaga New York 14227 Tel 888 SECUTRON 888 732 8876 Fax 905 660 4113 No part of this publication may be reproduced transmitted transcribed stored in a retrieval system or translated into any lan...

Reviews: