2.5.11 Mounting sampling stubs for the ceiling duct
Possible only with plastic tubes (PVC/ABS)!
The required parts of a sampling stub for the ceiling duct are
shown in
A T-piece is built into the sampling pipe at the required point.
The assembly sequence is performed as indicated by the
numbering
1
to
8
.
The size of the sampling hole (8) is based on the specification
in section “Planning” (T 131 192) and the specifications of the
“ASD PipeFlow” calculation software.
Notices
•
It is imperative to implement the interfaces of
the flexible tube “cleanly” so that the sealing
ring does not become damaged in the quick-
release coupling.
•
When clicking in the flexible tube, make sure
that the tube and quick-release coupling are
pressed well against each other to prevent
wrong air from being sucked in.
•
The maximum length of the flexible tube must
not exceed
1.5 m
.
Fig. 15 Mounting the ceiling duct
Flexible tube
Ø 16/21 mm
Length max. 1,5 m
Sampling
tube
False ceiling
Sampling hole
T-piece
M20 threaded ring
M20 quick-release
coupling
M20 quick-release
coupling
Sampling point /
M20 ceiling duct
1
8
2
3
5
6
7
4
M25 threaded ring