Digital Access Keypad Manual

SECO-LARM U.S.A., Inc.

Digital Access Keypad Manual

Note:

PLEASE ALSO REFER TO THE NOTES ON PAGE 6 FOR MORE GENERAL INFORMATION.

• The electromagnetic or electric door lock operation is the same as page 6, except the LED

outputs have changed.

• The function of the red and green LEDs depends on how they are connected to the alarm

control panel.

• Relay output #2 controls the arm/disarm of the alarm control panel. Consult the alarm

control panel manual for more information.

• Connect the duress output to a 24-hour N.O. zone and the tamper output to a 24-hour N.C.

zone on the alarm control panel.

• The connection of relay output #1 disable to output #3 as shown above is optional. When so

wired, output #3 is the inhibit control. To use, program output #3 for shunt on/off operation.
When output #3 is ON, relay output #1 will not work. For example, this prevents users from
entering the protected premises during the evening or weekend. See programming option
61. In this case, the center auxiliary LED changes from flashing green to steady red to show
that relay output #1 is disabled by the activation of output #3.

• The keypad's light green wire connects to the ground (-) wire of the alarm control panel to

enable the two to work together.

OUTPUT 1

EG

IN

N.C.

N.O

(+) (--)

Door

Sens

AUX LED

(for DC

use only)

Egress button (inside the

protected premises)

(+)

N.C. N.O.

12~24V AC/DC

C.

1      2     3      4     5      6     7      8     9     10    11   12    13    14    15    16

12VDC

power

supply

+

--

OR

Electric

Lock

Diode

1N4004

Cathode

N.O.

Additional egress buttons

can be connected in

parallel as needed

N.O.

REMARKS:

Output relay #1

N.O. output for fail-secure lock.

N.C. output for fail-safe lock.

OUTPUT

3

O/P 1 DISABLE

WHITE/ORANGE
LIGHT GREEN
PURPLE
BLUE
WHITE/BROWN
YELLOW
LIGHT BLUE
GREEN
GREY
BLACK
RED

N.O.
(--)
N.C.
N.O.
COM
(+)
(--)
(+)
(--)

N.C.

Duress -- To 24-hour N.O. zone
Com gnd (--) of keypad & alarm system
Relay output #2
Alarm arm/disarm control --
Consult alarm system manual for how
to connect for N.C. or N.O. operation

Red LED

Green LED

Tamper --
To a 24-hour N.C. zone

}

}

}

}

WIRING:

Example Wiring, with Connection to Lock Device and Alarm Arm/Disarm

+

--

ALARM CONTROL PANEL

Interlock

 -- Each keypad can be used as a stand-alone keypad. The mantrap feature is for a protected area with

two doors to ensure only one door is open at a time. With the mantrap feature, when a user keys in the code to
open one door, a signal is sent to the second keypad to disable it, thereby preventing access through the second
door until the first door is closed.

Note:

 

PLEASE ALSO REFER TO THE NOTES ON PAGE 6 FOR MORE GENERAL INFORMATION.

Use an N.C. magnetic contact or some other N.C. device to detect whether a door is opened or closed. Do this
for the two entrances to the protected premises.

The function of the red and green LEDs depends on how they are connected.

Combine this wiring diagram with the diagram on page 7 if connection to an alarm control panel is required.

Connect output #3 to relay output #1 disable as shown on page 6 if inhibit control is required.

To use the mantrap feature:
o Use either the keypad from outside or the egress button from inside the protected premises to open one of

the two doors.

o While the first door is opened, the first keypad sends a signal to the second keypad to prevent the second

keypad from being used to open the second door.

o After the first door is closed, both keypads are ready to use.

OUTPUT 1

EG

IN

N.C.

N.O.

(+) (--)

Door

Sens

GREEN LED 

(-

-)

O/P 1 Disable

(for DC

use only)

Egress button (open door 1 from inside).

Additional egress buttons can be

connected in parallel as needed.

GREEN LED 

( +

)

(+)

N.C. N.O.

12~24V AC/DC

C.

1      2     3      4     5      6     7      8     9     10    11   12    13    14    15    16

12VDC

power

supply

+

--

Electric

Lock

N.O.

REMARKS:

Output relay #1

N.O. output for fail-secure lock.

N.C. output for fail-safe lock.

LEDs:

Each LED requires a 1.5K-Ohm

series resistor for 24V operation.

+

--

Door 1

sensor

N.C

OR

To

 

(-

-) GND

To

 

O/P

 1 N.O.

Mantrap control

Common GND

OUTPUT 1

EG

IN

N.C.

N.O.

(+) (--)

Door

Sens

GREEN LED 

(-

-)

(for DC

use only)

Egress button (open door

2 from inside)

GREEN LED 

( +

)

(+)

N.C. N.O.

12~24V AC/DC

C.

1      2     3      4     5      6     7      8     9     10    11     12    13    14    15    16

12VDC

power

supply

+

--

Electric

Lock

N.O.

REMARKS:

Output relay #1

N.O. output for fail-secure lock.

N.C. output for fail-safe lock.

LEDs:

Each LED requires a 1.5K-Ohm

series resistor for 24V operation.

+

--

Door 2

sensor

N.C

OR

To

 

(-

-) GND

To

 

O/P

 1 N.O.

DOOR 1

DOOR 2

O/P 1 Disable

Mantrap control

Common GND

WIRING:

Example Wiring, Mantrap Using Two Keypads

Diode

1N4004

Cathode

Diode

1N4004

Cathode

LEDs:

For alarm status

indication. Each LED

requires a 1.5K-Ohm

series resistor for

24V operation.

}

Page 10

Page 7

Summary of Contents for Enforce SK-1131-SQ

Page 1: ...specifications printed in this manual are current at the time of publication However the SECO LARM policy is one of continual development and improvement For this reason SECO LARM reserves the right t...

Page 2: ...nd 14 to make any changes to the keypad s data 3 Exit the programming mode by pressing the key 1 Disconnect the power supply 2 Move the DAP jumper from OFF to ON 3 Reconnect the power supply The keypa...

Page 3: ...silent alarm if an authorized user is forced under duress to use the keypad The duress output is activated by adding 2 to the first digit of any user code for output 1 In this case the protected door...

Page 4: ...2 3 USER PROGRAMMING ADDING OR CHANGING MASTER AND USER CODES Note No user code may be the same as the master code Note For User ID key in he number of the user For Access Code type in the code for th...

Page 5: ...lts PROGRAMMING NOTES STATUS 1 In programming mode 2 Successful key entry 3 Successful code entry 4 Unsuccessful code entry 5 DAP jumper not replaced 6 In standby mode 7 Output relay activated BUZZER...

Page 6: ...trol is used all personnel must exit the protected premises before output 3 is activated Otherwise personnel in the protected premises will not be able to exit until output 3 is turned OFF The user co...

Page 7: ...ature is for a protected area with two doors to ensure only one door is open at a time With the mantrap feature when a user keys in the code to open one door a signal is sent to the second keypad to d...

Page 8: ...37 38 39 40 41 42 43 44 45 46 47 48 49 USER ID User Name Access Code 00 SAMPLE John Doe 54321 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 8...

Reviews: