INSTALLATION & TESTING
3
Testing
1. Plug a test telephone into the RJ connector of the SED-VTI and ensure you can
make a phone call (dial the receiver number).
2. Remove the test phone and connect the panel to the RJ port.
3. Trigger the panel to dial out. The H LED should turn on when the line is being
used.
4. When phone call is completed the H LED should turn off.
1. Install the unit at least 1 meter away from the alarm panel.
2. Fit the Sec-Eng Systems supplied antenna.
3. Fit SIM card. See page 2 for instruction on SIM type and checks.
4. Power up the unit with 12-14V DC from alarm panel.
5. Once the system is ready, the P LED should be on constant (not flashing) and
LEDs 1-5 indicating the signal strength (minimum of 2 bars is required).
6. Connect the phone lead from the panel to the RJ connector on the SED
–VTI.
7. Check the alarm panel is programmed with the phone number to dial (SED-VTI
only provides the phone line and doesn’t require any programming).
WARNING
• The SED-VTI is only to be installed by an authorised service person.
• The unit requires a power supply, 12-14V DC, 200mA.
• Ensure the unit is mounted in a safe & secure location, with the antenna in an
UPRIGHT
position.
• When installing in exposed areas, ensure that the antenna is covered in
20mm conduit to prevent tampering.
The above points should be taken seriously. Failing to abide by these
may result in the product not performing as designed.
Installation