The control unit is supplied by the manufacturer with the
possibility of selecting only the functions of the main menu.
To enable the functions of the extended menu follow this
procedure: press the SET key continuously for 5 seconds, the
T. MOT. and T. PAUSA LED’s flash alternatively and the user
has 30 seconds time to select the functions of the extended
menu with the SEL and SET keys, after 30 seconds the control
unit returns to the main menu.
---------------------- EXTENDED MENU -----------------
LED status
LED off
LED on
A) FUN. IN/OUT
remote PGM = OFF
remote PGM = ON
B) CODE
Photoelectric cells test = ON Photoelectric cells test =
OFF
C) CODE PED.
Pressure Maint. = OFF
Pressure
Maint. = ON
D) INB.CMD.AP
Electronic brake = OFF
Electronic
brake = ON
E) LAMP/CORT/CO
Closure strike = OFF
Colpo chiusura = ON
F) THE ARIES EFFECT
Not used
G) T. MOT.
Flashing beacon ON/OFF
H) T. PAUSA.
Flashing beacon ON/OFF
A) FUNCTION IN/OUT
(Remote programming of radio control) :
The control unit allows for programming the transmission code
from remote, without using the SEL key.
To programme the transmission code from remote follow this
procedure: send the radio control code continuously for more
than 10 seconds, the control unit enters the programming mode
as illustrated above for the CODE LED in the main menu.
The control unit is supplied by the manufacturer with the
remote programming of the transmission code not enabled; to
enable the function follow this procedure: check that the
extended menu is enabled (T. MOT. and T. PAUSA LED’s start
flashing alternatively), with the SEL key go to FUNCTION
IN/OUT LED when flashing and press the SET key: the
FUNCTION IN/OUT turns on and programming is completed.
Repeat the operation to restore the previous configuration.
B) CODE (Photoelectric Cells Test):
The control unit is supplied by the manufacturer with the
photoelectric cells test is enabled (in compliance with EN
12453); to disable the function follow this procedure: check that
the extended menu is enabled (T. MOT. and T. PAUSA LED’s
start flashing alternatively), with the “SEL” key go to CODE LED
when flashing and press the “SET” key: the CODE turns on and
programming is completed. In this way the photoelectric cells
test is not performed; also if they are not connected (if not
used, DS2 input must be bridged) the control unit is enabled for
operation. Repeat the operation to restore the previous
configuration.
C) CODE PED: (Maintenance of Hydraulic Motor Pressure):
The control unit is supplied by the manufacturer with the
maintenance of hydraulic motor pressure not enabled. To
enable the function follow this procedure: check that the
extended menu is enabled (T. MOT. and T. PAUSA LED’s start
flashing alternatively), with the SEL key go to CODE PED LED
when flashing and press the SET key: the CODE PED LED
turns on and programming is completed. In this way the control
unit will send a closing command to the motor every 2 hours for
2 seconds. Repeat the operation to restore the previous
configuration.
D) INB. CMD. AP (Electronic Brake):
The control unit is supplied by the manufacturer with the
electronic brake function not enabled. To enable the function
follow this procedure: check that the extended menu is enabled
(T. MOT. and T. PAUSA LED’s start flashing alternatively), with
the SEL key go to INB. CMD. AP. LED when flashing and press
the SET key: the INB. CMD. AP. turns on and programming is
completed. The control unit reduces the forward motion of the
gate due to inertia in the presence of a stop or inversion
command. Repeat the operation to restore the previous
configuration.
E) LAMP/CORT/CO (Closure Strike) :
The control unit is supplied with the closure strike function not
enabled. To enable the function follow this procedure: check
that the extended menu is enabled (T. MOT. and T. PAUSA
LED’s start flashing alternatively), with the SEL key go to
LAMP/CORT/CO LED when flashing and press the SET key:
the LAMP/CORT/CO LED turns on and programming is
completed. If programmed with deceleration during closing, the
control unit will add a 1-second time at maximum power (after
completing the decelerated closing operation) to overcome the
lock, if any. Repeat the operation to restore the previous
configuration.
RESET :
To reset the default configuration, press the SEL and SET keys
simultaneously, all
RED
LED’s will turn on and then off.
DIAGNOSTICS:
Photoelectric Cells Test:
The control unit is set for the connection of safety devices
compliant with 5.1.1.6 section of EN 12453. The operation test
of connected photoelectric cells is performed at each
manoeuvring cycle. In case of no connection and/or no
operation, the control unit will not enable movement and will
visually indicate the test failure with simultaneous flashing of all
LED’s. Once the correct operation of the photoelectric cells has
been restored, the control unit is ready for operation. This
guarantees monitoring against failures in compliance with
Category 2 of EN 954-1.
Command input test:
The control unit is provided with a LED for each low voltage
command input to monitor the status immediately.
Operation principle: LED on = input closed, LED off = input
open.