background image

5.  maintenance

5.1.    

The extinguishers should be visually inspected at least quarterly, but preferably monthly, by the user, to ensure that the equipment is in  

 

its designated position, has not been used and has not been tampered with. The servicing of fire fighting equipment must be carried  

 

out by a competent person using the correct tools to follow the procedures of BS 5306 part 3, 2003 and the manufacturers instructions.  

 

This maintenance should be performed at least annually.

5.1.1.   

Inspect regularly for damage and operational serviceablility.

5.1.2. 

  

If pressure indicator is in the red zone recharge the extinguisher.

 

Do not

 test prior to use.

5.1.3.   

Check servicability at least annually in accordance with BS 5306 PART 3:2003.

5.1.4. 

  

Recharge after complete or partial use.

5.1.5. 

  

Refilling and servicing should be carried out by a competent person in accordance with BS5306-9:2015 

 

5.1.6.   

Use only product and spare parts approved by the manufacturer for this model.

5.1.7.   

Refill charge: 6 litres (100%). Water: 5.82 litres (97%), AFFF: 0.18 litres (3%). Pressurised with nitrogen to a working pressure of 12  

 

bar at 20

0

C.

5.1.8. 

  

Storage/operating temperature range :  +5

0

C to + 60

0

C. Protect from frost.

5.1.9.   

Test pressure (PT): 27 bar.

  

 

Original Language Version

© Jack Sealey limited

sealey group, Kempson Way, suffolk Business park, Bury st edmunds, suffolk. ip32 7ar

 01284 757500 

 01284 703534 

 [email protected] 

 www.sealey.co.uk

environment protection

Recycle unwanted materials instead of disposing of them as waste. All tools, accessories and packaging should be sorted, taken to 
a recycling centre and disposed of in a manner which is compatible with the environment. When the product becomes completely 

unserviceable and requires disposal, drain any fluids (if applicable) into approved containers and dispose of the product and fluids 

according to local regulations.

note

: It is our policy to continually improve products and as such we reserve the right to alter data, specifications and component parts without prior 

notice.

important

: no liability is accepted for incorrect use of this product.

Warranty

: Guarantee is 12 months from purchase date, proof of which is required for any claim.

S

FE06    Issue 2 (H, 4, 5, F) 12/11/18