Sealey SCMA1 Manual Download Page 4

7.5.    

LOCKING  RELEASE

7.5.1.    Press the TEST button, the unit will return to Normal Operation status, see fig.3.

7.6.    

ALARM  CONDITION

7.6.1. 

  

When the unit detects dangerous levels of CO, it will emit an alarm signal along with flashing red LED, see fig.4. This will continue  

 

as long as there is a dangerous level of CO concentration of or equal to 5PPM. The LCD will show the concentration and SPEAKER  

 

symbol. This will indicate that an alarm has occurred and it should be investigated.

NOTE:

   To stop the alarm refer to 7.4.

7.7.    

MEMORY  FUNCTION

7.7.1. 

  

When no one is home, the unit may detect CO and the alarm sound. The alarm stops when the CO condition returns to normal. The  

 

highest CO concentration that was present, will be recorded and shown on the LCD with the “CO figure” flickering once every 15   

 

seconds, together with 2 continuous “beep”, “beep” sounds, red LED and the “SPEAKER” symbol flashing, see fig.6.

7.7.2. 

  

Press the TEST button, the “CO figure” will then be cleared and the unit returns to normal working condition, see fig.3.

7.8.    

LOW BATTERY SIGNAL

7.8.1.   

When the unit detects the battery voltage is low and needs replacing, the red LED will beep every 40 seconds along with one BEEP.  

 

The LCD will show the LOW VOLTAGE symbol, see fig.6. 

7.8.2. 

  

The

 red LED will flash as usual, during the low battery period, and the unit can still alarm as usual.

NOTE:  

The normal stand by time of battery is 5 years minimum. If there is a problem with the battery or low battery signal warning  

 

 

  keeps activating for over 30 days, replace the battery.

7.9.    

MANUAL  ZERO

7.9.1.   

In normal operation with no CO gas present, when the LCD does not show “0 PPM”, you can press the TEST button down for 3    

 

seconds until the PPM character on the LCD disappears, then release the TEST button until the LCD shows “0 PPM”. 

7.9.2. 

  

Manual Zero can only be carried out under the following two conditions: 

 

A: The CO concentration on the LCD is lower than 10 PPM.

 

 

B: The first digit of the LCD shows “-”.

7.10. 

FAULT SIGNAL WARNING 

7.10.1.  T

he unit will self-test the amplifying circuit and sensor every 10 seconds.  

 

 

When there is a problem with the amplifying circuit or sensor,the unit   

 

 

will beep every 30 seconds along with a yellow flashing LED, the LCD  

 

 

will show “---”, see fig.7.

CO - LEVEL (PPM)

RESPONSE TIME (MIN.)

ALARM SOUND

30 ppm - 49 ppm

After 120

2 continuous chirp (with 1 s frequency chirp)

50 ppm - 99 ppm

60 - 90

3 continuous chirp (with 1 s frequency chirp)

100 ppm - 299 ppm

10 - 40

4 continuous chirp (with 1 s frequency chirp)

300 ppm or above

0 - 3

4 continuous chirp (with 0.5 s frequency chirp)

Flashes every 40

seconds

   fig.6

   fig.8

Flashes every 60

seconds

   fig.7

Flashes every 30

seconds

S

CMA1 Issue 2 23/06/2020

Original Language Version

© Jack Sealey Limited

Summary of Contents for SCMA1

Page 1: ...s of carbon monoxide poisoning and how to operate the CO alarm 9 Test your CO alarm once a month 9 Replace low batteries immediately 9 Only purchase approved combustion devices 9 Install combustion devices in the correct way and strictly follow the instructions of the manufacturer 9 Have any installations carried out by a professional 9 Have your installations checked by a qualified installer on a...

Page 2: ...y or greasy emissions could contaminate or clog the sensor behind curtains or furniture in the path of air discharged from a furnace air conditioning vent or ceiling fan outside the building directly above a sink or cooker WARNING This carbon monoxide alarm is designed for indoor use only DO NOT expose to rain or moisture It will not protect against the risk of carbon monoxide poisoning when the b...

Page 3: ...d in the LCD after the batteries have been installed Though this alarm can self diagnose the amplifying circuit and sensor it is recommended that you test your CO alarm once a month to ensure it is working correctly 7 4 ALARM LOCKING 7 4 1 If the TEST button is pressed again whilst the CO alarm is sounding the alarm will move into LOCKING status and the red LED and the green LED will flash every 1...

Page 4: ...LED will flash as usual during the low battery period and the unit can still alarm as usual NOTE The normal stand by time of battery is 5 years minimum If there is a problem with the battery or low battery signal warning keeps activating for over 30 days replace the battery 7 9 MANUAL ZERO 7 9 1 In normal operation with no CO gas present when the LCD does not show 0 PPM you can press the TEST butt...

Page 5: ...o ventilate the area and allow the carbon monoxide to disperse 7 13 2 Where possible to turn off any fuel burning appliance 7 13 3 Evacuate the building DO NOT re enter the premises or move away from the open door window until emergency services have arrived the premises have been aired out and your alarm has returned to its normal condition 7 13 4 Seek medical help immediately for anyone sufferin...

Page 6: ...l regulations BATTERY REMOVAL SEE SECTION 7 1 Under the Waste Batteries and Accumulators Regulations 2009 Jack Sealey Ltd are required to inform potential purchasers of products containing batteries as defined within these regulations that they are registered with Valpak s registered compliance scheme Jack Sealey Ltd Batteries Producer Registration Number BPRN is BPRN00705 Note It is our policy to...

Reviews: