Original Language Version
© Jack Sealey Limited
6.2.
SETTINGS
6.2.1.
START UP AND SHUTDOWN
6.2.1.1.
Press POWER to turn the unit ON (fig.10 #4).
6.2.1.2.
Press MODE button to select the desired operation mode (fig.10 #2).
6.2.1.3.
Press POWER again to turn the unit OFF (fig.10 #4).
6.2.2.
OPERATION MODE
The unit has four operation modes: Cool, dehumidifier, fan and sleep.
6.2.3.
COOLING A ROOM
6.2.3.1.
Select the COOL mode to lower the temperature in a room.
6.2.3.2.
Press MODE button (fig.10 #2) until the COOL indicator illuminates (fig.10 #10).
6.2.3.3.
Press the UP or DOWN button (fig.10 #3 #5) to adjust the temperature to the desired level. The temperature will be displayed on
the screen (fig.10 #9). The temperature can be set between 16ºC to 32ºC.
6.2.3.4.
Press the Speed button (fig.10 #6) Until the desired fan speed indicator illuminates (fig.10 #8).
NOTE:
The horizontal air flow direction is controlled by adjusting the air outlet louvres (fig.1 #2).
WARNING!
The air conditioner function will stop if the room temperature is lower than the selected temperature.
6.2.4.
VENTILATE
THE ROOM
6.2.4.1.
Press the MODE button (fig.10 #2) until the FAN indicator illuminates (fig.10 #10).
NOTE:
In ventilation mode the room air is circulated NOT cooled.
6.2.4.2.
Press the Speed button (fig.10 #6) Until the desired fan speed indicator illuminates (fig.10 #10).
6.2.5.
DRYING THE ROOM
6.2.5.1.
Press the MODE button on the control panel (fig.10 #2) until the DRY indicator illuminates (fig.10 #10), or press the DRY button on
the remote control (fig.11).
6.2.5.2.
Connect the drain hose (fig.1 #13) To the drain outlet at the bottom of the unit (fig.1 #6). See section 6.5.
NOTE:
In this mode the fan speed is set to low level and cannot be changed.
6.2.6.
SLEEP MODE
WARNING!
This function can only be activated by using the SLEEP button on the remote control (fig.11).
To activate the sleep mode the unit must be in the COOL mode.
6.2.6.1.
To activate COOL mode press the COOL button on the remote control and then press the SLEEP (fig.11).
NOTE:
After 1 hour the pre-set temperature is increased by 1ºC and increased again by 1ºC the following
hour.
6.2.7.
TIMER SETTING (1 to 24 hours)
6.2.7.1.
The TIMER has two ways of operation and can be activated by either the button on the control panel
(fig.10 #7) or by the TIMER button on the remote control (fig.11).
6.3.
AUTOMATIC DEFROST
During use if operating at low room temperatures frost may build up at the evaporator. The POWER indicator will start to blink and
the unit will automatically begin to defrost.
The defrost control sequence is as follows:
A
. If operating the unit in either the cooling or drying mode, the ambient temperature sensor senses that the evaporator coil
temperature is below -1ºC the compressor will stop. It will restart again, in the COOL mode, after 10 minutes or when the coil
reaches the temperature of 7ºC.
B
. If operating the unit in the drying mode, the coil temperature sensor senses that the temperature of the evaporator is below 40ºC
and the differential temperature between the coil temperature and the ambient room temperature is below 19ºC and the compressor
has been in operation for twenty minutes the unit will start defrosting for five minutes and the POWER indicator will begin to
blink.
6.4.
OVERLOAD PROTECTION
If there is a loss of power, to protect the compressor, there is a three minute delay until the
compressor will restart.
6.5.
MANUAL DRAINAGE
NOTE:
When the unit is full of water it will automatically shut off.
6.5.1.
Switch off the unit and remove the electrical plug from it’s power source.
6.5.2.
With care move the unit to suitable location to enable a container to be located below the
bottom drainage hole (fig.1 #6).
6.5.3.
With the container in place remove the drain plug (fig.12).
WARNING!
The water will flow out instantly from the drainage hole.
6.5.4.
When the unit has completely drained replace the drain plug back fully into the drainage hole.
NOTE:
To assist with drainage the unit can be slightly tilted backwards to allow the drain plug to
be re-inserted if the container becomes full.
6.5.5.
Replace the electric plug into the power source and re-start the appliance in the desired mode.
WARNING!
Ensure that the drain plug is fully inserted, otherwise the condensate water will flow
out onto the floor.
fig.12
fig.11
S
AC7000 Issue 3 (3) 15/06/22