REMINDER: Sea-Fire systems shall be considered as supplementary to the number of portable
fire extinguishers required on-board and are designed and intended for enclosed unoccupied
compartment installations that are not subject to direct weather or water.

SYSTEM OPERATIONS

Sea-Fire units described in this manual are automatically actuated by a heat actuated tube.
Discharge will occur as a result of direct flame impingement. The Sea-Fire FT system uses
the supplied length of temperature sensitive tubing as both detection and delivery system.
The tubing should be routed close to the hazard, where fire is likely to occur, but away from
heat sources that could accidentally cause it to operate. Upon flame impingement, the tubing
will rupture, and the extinguishing agent will discharge through the rupture point. No separate
discharge nozzle is needed.

CAUTION: IN CASE OF EXTINGUISHER DISCHARGE, DO NOT RUSH TO OPEN THE
PROTECTED COMPARTMENT. LET THE EXTINGUISHING AGENT WORK FOR SEVERAL
MINUTES. HAVE A PORTABLE EXTINGUISHER AVAILABLE AND USE CARE WHEN
OPENING THE COMPARTMENT.

AVOID BREATHING FIRE RELATED FUMES OR VAPOR.

NOTE: It is important to retain the designed vapor concentration within the compartment to
insure complete fire outage. Upon discharge, all powered ventilation (blowers) must be shut
down.

PRESSURE SWITCH

Sea-Fire “FT” series extinguishers are equipped with a factory installed pressure switch which
is intended for cylinder pressure supervision and may also be used to control other electrical
functions (engine shutdown, air exchange equipment, electric supply, etc.)

When using the pressure switch as an electrical disconnect for any equipment shutdown
function, a means of overriding (bypassing, shunting) the pressure switch must be provided
in order to return the affected equipment to an operational mode after extinguisher discharge
has occurred. The pressure switch is a single pole single throw (SPST) type that is normally
closed (NC) with the system in the charged condition. Discharge or loss of system pressure
will release the contacts to an open state thereby cutting off any electrical current flow.

NEVER USE PRESSURE SWITCH FOR ELECTRICAL LOADS OVER RATED CAPACITY.

SWITCH SPECIFICATIONS

4.0 AMPS AT 12 VDC

2.0 AMPS AT 28 VDC

For applications requiring larger load capacities, see OPTIONAL EQUIPMENT section IN
THIS manual or contact factory.

DIESEL ENGINES

Continued operation of diesel engine(s) and or powered ventilation units will deplete the
extinguishing agent and may cause a fire re-flash. Diesel engine(s) must be automatically
shutdown upon extinguisher discharge.

Note: Power ventilation (blowers) that exceeds one air change per minute within the protected
compartment must be automatically shutdown upon extinguisher discharge.*

*ABYC requirement - Standard A-4

GASOLINE ENGINES

WARNING: GASOLINE ENGINES AND FANS SHOULD BE AUTOMATICALLY OR
MANUALLY SHUT DOWN AT TIME OF DISCHARGE.

Shutdown may be accomplished by interruption of the electrical circuit between the ignition
switch and the engine coils.

NOTE: Sea-Fire optional engine interrupt systems will automatically shut down engines and
powered ventilation upon discharge of the fire SUPPRESSION system. They are available in
12 and 24-volt models with 3, 5 or 8 control circuits, refer to OPTIONAL EQUIPMENT section
in this manual.

3

Summary of Contents for FM200

Page 1: ... MUST BE INSTALLED AND MAINTAINED ACCORDINGLY READ AND COMPLY WITH THESE INSTRUCTIONS WARNINGS AND LIMITATIONS BEFORE INSTALLING SUITABLE FOR USE FT MODELS 32 F 130 F 0 C 54 C ALWAYS MAINTAIN THIS OWNER S MANUAL NEARBY FOR OPERATOR REFERENCE APPROVALS FACTORY MUTUAL FM 3022058 U S COAST GUARD U S C G 162 029 241 REV A PRINTED IN USA PART NO 123 186 ...

Page 2: ...ed compartment The specification table in this manual lists the minimum and maximum approved compartment volume size allowable for each model Volume can be determined by multiplying the compartment s length x width x height which equals the volume in cubic feet or meters LxWxH V Exception If the boat manufacturer has placed a permanently affixed label in the compart ment specifying the gross volum...

Page 3: ...ment electric supply etc When using the pressure switch as an electrical disconnect for any equipment shutdown function a means of overriding bypassing shunting the pressure switch must be provided in order to return the affected equipment to an operational mode after extinguisher discharge has occurred The pressure switch is a single pole single throw SPST type that is normally closed NC with the...

Page 4: ...ERSIDE OF COVER OR COM PARTMENT HATCH THAT COULD BE THROWN CLEAR DUE TO POSSIBLE EX PLOSION 8 DO NOT MOUNT WHERE AN ACCUMULATION OF STANDING WATER COULD BLOCK SENSOR OR CAUSE CORROSION 9 EXTINGUISHER TO BE MOUNTED IN THE VERTICAL POSITION ONLY 10 DO NOT USE FOR PRIMARY ENGINE COMPARTMENT PROTECTION EXTINGUISHER INSTALLATION Step 1 Carefully remove extinguisher from carton and visually check for da...

Page 5: ...ssembly Note Do not kink tub ing if kink occurs remove effected area with razor Step 10 Tighten fitting and tube to cylinder using 1 2 12mm wrench Preferred torque value is 3 4 1 2 inch pounds of force Overtightening may cause tube to rupture Step 11 Activate system Using a straight screwdriver open valve VERY SLOWLY counter clockwise 1 4 of a turn to allow detection tube to fill with nitrogen Not...

Page 6: ...oper range 2 Check fuse and indicator light and replace if defective lamp replacements available from factory 3 Check for loose electrical connections 4 Remove and weigh system cylinder as described in MAINTENANCE Section of the manual INDICATOR LIGHT INSTALLATION Select a location at the helm on or near the console that is in full view of the helmsman the location selected must have access for el...

Page 7: ...nd tools Attach one wire lead from the in line fuse to the ignition position on the starter switch Connect other lead from the in line fuse to the indicator light Connect remaining indica tor lead to one of the Sea Fire cylinder pressure switch connector wires Connect the remaining cylinder pressure switch lead to common ground which may be the negative battery buss at the control panel or directl...

Page 8: ... audible system status indicator with override switch for engine restart Avail able with 3 5 or 8 control circuits in 12 or 24 VDC models ESRS WT III V VIII Same as ESRS MARK shutdown system but also includes a factory installed nominal 20 second release timer on the engines control cir cuits For use in diesel engines that shutdown through activation of a momentary device i e push button lever etc...

Page 9: ...ystem for one half of the current suggested list price RETURN TO UNITED STATES EUROPE SEA FIRE MARINE SEA FIRE EUROPE LTD Division of Metalcraft Inc Unit 7 io Centre Stephenson Road 9331 A Philadelphia Road Fareham Hampshire Baltimore Maryland 21237 USA PO15 5RU United Kingdom Website www sea fire com EQUIPMENT LIST FOR INSTALLATION 1 Drill motor 2 Drill bit 25 64 390 for rubber grommet 3 Drill bi...

Page 10: ...MPERATURE RANGE 32 F 130 F 0 C 54 C STANDARD EQUIPMENT LIST SUPPLIED WITH EACH SYSTEM 1 ONE TUBING KIT PART 130 121 10 FOOT TUBE OR 130 122 15 FOOT TUBE 2 ONE BRACKET ASSEMBLY Model Bracket Part FT 25 122 010 FT 50 122 010 FT 75 122 010 FT 100 130 011 FT 125 130 012 FT 150 130 013 10 ...

Page 11: ... property damage if the valve is broken due to improper handling or storage Section 4 First Aid Measures Skin contact Flush with water treat for frostbite if necessary by gently warming affected areas Consult a physician Eye contact Immediately flush eyes with plenty of water for at least 15 minutes Consult an ophthalmologist Inhalation Remove victim s to fresh air as quickly as possible If not br...

Page 12: ...nimal Routes Components 788 696 ppm 4H Rat Acute Inhalation 1 1 1 2 3 3 3 Heptafluoropropane The human health hazards of this product are expected to be similar to other liquefied gases including N2 C02 CFCs HCFCs and HBFCs Therefore direct eye or skin contact with the liquid or cold gas can cause chilling or possibly frostbite of exposed tissues Inhalation of high concentrations can be harmful or...

Page 13: ... DISCLAIMER OF EXPRESSED AND IMPLIED WARRANTIES Metalcraft Sea Fire Marine Inc has taken reasonable care in preparing this document how ever since the use of this information and the conditions of use of the product are not within the control of Metalcraft Sea Fire Marine Inc it is the user s obligation to determine the conditions of safe use of this product The information in this document is off...

Page 14: ...MARINE SEA FIRE EUROPE LTD Division of Metalcraft Inc Unit 7 io Centre Stephenson Road 9331 A Philadelphia Road Fareham Hampshire Baltimore Maryland 21237 USA PO15 5RU United Kingdom Website www sea fire com 14 ...

Reviews:

Related manuals for FM200