SE Controls SHEVTEC Technical Information And Operating Instructions Download Page 4

 

 

 
 
 
 
 
 

              1.0 Important Notices 

 

 

Use of abrasive or solvent cleaning products may damage the panel 

 

Taken care when fault finding or servicing to retain device addresses. 

 

 

 

   2.0 Parts 

 

The SHEVTEC® Repeater Panel comprises: 

 

SHEVTEC® Repeater Panel 

 

Mounting Plate 

 

Torx locking screw 

 

Not supplied but required: 

 

Installation of one or more OS2 OSLink or OSLoop Coordinator 

 

Four core fire rated cable 

 

Wall fixings and screws 

 

 

     3.0 Tools Required 

 

 

Drill for wall fixings 

 

Spirit level 

 

Screwdriver 

 

Wire cutters and strippers 

 

Torx screwdriver 

 

Optional multimeter 

 

OSLoop systems require the parameter [OADD] set – this may be preset at the factory or may require use of an 

SEC POP configuration tool. 

 

  

4.0  Preparation 

 

SHEVTEC® Repeater Panels are custom built for each application. After unpacking the SHEVTEC® Repeater Panel 
and check the reference printed on the data badge is correct. 

 

 5.0 Cable installation 

 

Install a four-way fire rated cable between the nearest OS2 or OSLoop Coordinator and the required location of 

the panel. Where cables are buried in the wall, ensure the wall is flat over the area of the panel and that the cable 

is brought to the centre of the desired location. Leave 200-300mm spare cable at the repeater. 
 
 
 
 

Summary of Contents for SHEVTEC

Page 1: ...SHEVTEC Repeater Panel Technical Information and Operating Instructions...

Page 2: ...of zone indicators Each zone indication comprises a green healthy yellow fault and red active LED Each zone indication may be controlled by to any OS2 device any zone of an OSLoop system or configured...

Page 3: ...plate 4 7 0 Binding addresses OS2 4 8 0 Binding addresses OSLoop 4 9 0 Connection to OSLoop Coordinator 5 10 0 Connection to OS2 with OSLink 5 11 0 Address and DIP Switch 7 12 0 Connection to the SHEV...

Page 4: ...s Torx screwdriver Optional multimeter OSLoop systems require the parameter OADD set this may be preset at the factory or may require use of an SEC POPconfiguration tool 4 0 Preparation SHEVTEC Repeat...

Page 5: ...e bottom left corner For OS2 bindings this is a single digit number The OSLink addresses set on the OSLink card rotary address switch must beset to match each LED zone After changing OS2 OSlink addres...

Page 6: ...resetting fuse 10 0 Connection to OS2 with OSLink Ensure the OS2 system is powered down before proceeding Signal Device Terminal FP 4 core and earth 1 5mm OS2 Data A NTA Blue Data B NTB Brown Power V...

Page 7: ...6 When the cable has an overall screen the screen may optionally be connected to the OS2 SCR terminal...

Page 8: ...re set off at the factory 12 0 Connection to the SHEVTEC Repeater Panel Connection to the SHEVTEC Repeater Panel is made using a pluggable terminal block CN3 Connections are labelled on the rear of th...

Page 9: ...mplete 14 0 Recommended Maintenance The SHEVTEC Repeater Panel requires no maintenance and contains no replaceable parts Operation of the LEDs and sounder may be tested using the lamp test button When...

Page 10: ...he panel audible alarm The alarm override will remain until the cause of the alarm is cleared On OSLoop systems the silence button will also globally silence the local sounders at the coordinators and...