SE Controls SECO Ni Technical Information And Operating Instructions Download Page 6

+44 (0)1543 443060 

[email protected] 

www.secontrols.com

Installation Guide - Door Applications

1. 

Ensure door is free and clear of 

all obstructions and debris.

2. 

Install the Supplied pivot 

bracket set to the actuator.

3. 

Off er actuator up to door with the 

door and actuator fully closed. Take 

measurement of the fi xing height 

required for the actuator not to touch 

the opening door when door opens/

closes.

4. 

Power the actuator to the fully 

open position.

5. 

Mark up the distance from the 

hinge to the actuator to allow 

the door to be opened to the 

required position.

6. 

Ensure the installation location 

allows for the actuator to open to 

the maximum opening angle.

7.

Mark up the bracket holes in all 

four positions.

8. 

Drive the actuator fully closed 

and allow the door to close, ensure 

the opening doesn’t clash with the 

actuator.

9. 

Fix actuator using screws 

suitable for the door 

construction.

Please keep these operating instructions for future 

reference and maintenance. Subject to technical 

modifi cations. Diagram is not binding.

10. 

Attach the slider bracket and 

bracket retention cable to the door. 

Cycle test the door open and closed 

multiple times to ensure correct 

operation.

11. 

Installation is complete, if 

required add fi nger entrapment 

stickers to the door.

Summary of Contents for SECO Ni

Page 1: ...instructions for future reference and maintenance Subject to technical modi cations Diagram is not binding SECO Ni Folding Arm Roller Version 24V dc Roller Folding Arm Smoke Environmental Ventilation...

Page 2: ...Operating Speed 15mm sec Ambient Operating Temp 5 C 60 C Thrust Force 400N Close Force 400N Soft Close Yes Switching Electronic Standard Finish Grey RAL 9006 Seal Relief Programmable up to 20mm Clamp...

Page 3: ...h attention must be paid All actuator products contain metallic plastic and electronic parts Redundant electronic products are classi ed as hazardous waste under the WEEE regulations Waste Electrical...

Page 4: ...of the cables in relation to the cable lengths and power consumption Care must be taken to ensure that actuator products are controlled with compatible products refer to SE Controls No liability will...

Page 5: ...All smoke ventilation systems must be periodically annually checked serviced maintained and if necessary repaired and re tested by a authorised trained and competent safety conscious persons Maintena...

Page 6: ...be opened to the required position 6 Ensure the installation location allows for the actuator to open to the maximum opening angle 7 Mark up the bracket holes in all four positions 8 Drive the actuato...

Page 7: ...5600 30 SE Controls is a Registered Trademark Lancaster House Wellington Crescent Fradley Park Lichfield Staffordshire WS13 8RZ Creating a healthier safer environment 44 0 1543 443060 sales secontrols...