INSTRUCTIONS

Open battery cover and install a 9V battery in the battery 
compartment.

Turn power ON and select the desired response time and 
weighting. If the sound source consists of short bursts or 
only catching sound peak, set response to FAST. To 
measure average sound level, use the SLOW setting.

Select desired Level.

Hold the instrument comfortably in hand and point the 
microphone at the suspected noise source, the sound 
pressure level will be displayed.

When MAX/MIN ( maximum, minimum hold ) mode is 
chosen. The instrument captures and holds the maximum 
noise level for a long period using any of the time 
weightings and ranges.

Press the MAX/MIN button 2 seconds to clear the 
MAX/MIN reading. “MAX/MIN” symbol disappears.

Turn OFF the instrument.

(1)

(2)

(3)

(4)

(5)

(6)

SPECIFICATIONS

Standard Applied:

 IEC651 Type2, ANSI S1.4 Type2.

 31.5Hz to 8KHz

Frequency Range:

 32dB to 130dB

Measuring Level Range:

 A / C

Frequency Weighting:

 ½ inch electrical condenser microphone

Microphone:

 LCD

Display:

 4 digit

Digital Display:

 0.1dB

Resolution:

 0.5 sec.

Display Update:

 FAST ( 125mS ), SLOW ( 1 sec. )

Time Weighting:

 Lo: 32 dB to 80 dB

Level Ranges:

                        Med: 50 dB to 100 dB

                        Hi: 80 dB to 130 dB

Accuracy:

      ±1.5dB ( under reference conditions, 94dB@1kHz )

 50 dB

Dynamic Range:

 “OVER” is when the input is more than upper 

Alarm Function:

limit of range.

“UNDER” is when input is less than lower limit of range.

MAX / MIN Hold:

   Hold readings the Maximum and Minimum Value.

 1 Vms at FS ( full scale ).

AC Output:

   Output impedence: Approx 100 Ohms

   FS: means the upper limit of each level range.

Power Supply:

   One 9V battery, 006P or IEC 6F22 or NEDA 1604.

 Approximately 70hours ( Alkaline Battery )

Power Life:

0 to 40°C ( 32 to 104°F )

Operation Temperature: 

Operation Humidity:

 10 to 75%RH

 9.1” L x 2.1” W x 1.3” H

Dimensions:

                     23.1 cm x 5.3 cm x 3.3 cm

 .75 lbs (.34kg) (including battery)

Weight:

9V battery, screwdriver, instruction manual and 

Accessories: 

windscreen.

WHY dBchecker?

Merely  "listening"  or  utilizing  any  sound  level  meter  available  is  not  a 
reliable method for testing audible alarm notification appliances. Many 
of the meters currently on the market do not meet the requirements for 
NFPA 72. 

dBchecker™

 conforms to ANSI S1.4a, which is required to 

meet  the  standard  set  forth  in  the  latest  edition  of    the  National  Fire 
Alarm Code. (NFPA 72)
 

HIGHEST STANDARDS

"  ….only  sound  level  meters  that  comply  with ANSI  S1.42  should  be 
used for the assessment of fore alarm systems…" 

" …Testing of Audible Alarm Notification Appliances shall be done upon 
initial acceptance and semi-annually" 

" …Sound pressure shall be measured with sound level meter meeting 
ANSI  S1.4a,  Specifications  for  Sound  Level  Meters,  Type  2 
Requirements.

 

Levels  throughout  the  protected  area  shall  be 

measured and recorded…."  

 

NFPA 72  14.4.2.2 (15)

CAN/ULC S536-04, G1.1 
" The sound level meter shall have a measurement range that permits 
readings as low as 35 dBA..." "The use of a quality meter to minimize 
any measurement errors. ANSI S1.40, Specifications for Acoustic 
Calibrators, is one standard that can provide guidance on the subject." 

LN, Oct

LT, Oct

Fire Alarm

Frequency (Hz)

10

100

1000

10,000

35

40

45

50

55

60

65

70

75

Sound Pressure Level (dB)

LI32187-4

ALSO AVAILABLE FROM SDi

 

Professional Smoke Detector Testers

    

with approved and listed dispensers

 

Genuine Professional Heat Detector Testers

    

suitable for fixed temperature, rate of rise and combined detectors

 

CO Detector Testers

    

with approved and listed dispenser

 

Aerosol Dispensing Tools

    

as recommended by detector manufacturers

 

Detector Removal Tools

   

suitable for all leading makes and model of detector

 

Access Poles

    

to enable detector maintenance up to 30+ ft.

 

Complete Maintenance and Service

    

providing complete solutions in economical and convenient kit formats

 

Smoke Detector Sensitivity Instruments

    

to identify sensitivity drift and help ensure that smoke detector sensitivity is 

     maintained within defined calibration parameters

SDi

,

1345 Campus Parkway, Neptune, NJ 07753-6815 USA
Tel: 732-751-9266   Fax: 732-751-9241
Email: [email protected]   Web: www.sdifire.com

Specialized Fire Products

Reviews: