Scully ST-15C Series Technical Manual Download Page 10

10

2.2.1 Power Connections

Route the mains power wires through the top left-hand entry hole in the top of enclosure.  Connect mains
power wires to appropriate terminals on terminal block (strip) on the metal bracket in the enclosure.  The
Power terminals are marked 

E, N,  & L

, also shown in wiring diagram.

NOTE:   

The ST-15C Control Module is protected by a 1A high interrupt capacity fuse in the enclosure.  The fuse (F1) is

located next to the terminal strip on metal bracket.

2.2.2 Enclosure Earth (Ground) Connection

Connect a wire (1.5mm

2

 minimum) from the enclosure-bonding stud to earthed metallic structure of the

gantry (rack).

2.2.3 Control Output (Controlled Circuit) Connections

Route the control output wiring through the top right hand entry hole in the enclosure and connect to output
contact terminals, indicated on the terminal strip on metal bracket. The output control contact is open when
no connection from the controller is made to a vehicle (idle state). The output control contact closes when
sensor connected to the control unit is dry and functional (or when optional bypass switch is in the “Bypass”
position).

The contact opens if sensor gets wet (i.e. detects liquid).  The contact also opens in case of a fault in the
sensor, wiring to the sensor or a fault within the control units’ circuitry.

NOTE:

  

An internal 5A high interrupt capacity fuse protects the output relay contact.  The fuse (F2) is located on

metal bracket.

The output contact is rated 250VAC, 5A resistive maximum.  It is used to close a valve or pump directly or
by wiring it in series with other control contacts, such as a preset meter’s control contacts.  (See Diagram
61441, Typical Loading Rack Control in Appendix 4.0.)  In addition it may also be connected to an input of a
terminal automation system (TAS) to provide status of the controller’s output to TAS.

Caution: 

A valve or pump should be directly controlled by ST-15C’s relay output contact.  It should not go

via the logic circuits of a TAS, as that can introduce unsafe failure modes into this emergency shutdown
system.  TAS may also control a valve or pump based on other conditions.

2.2.4 Intrinsically Safe Connections to Sculcon Plug & Cable Unit

Signals from ST-15C to Sculcon Plug & Cable Unit are intrinsically safe. The intrinsically safe connections
must only be made via the entry hole in the bottom of the enclosure.  The connections are made to the
terminal strip TB2 at the bottom end of the printed circuit board module.  The wires must be 1.5mm

2

(18AWG) minimum conductor size.  Connect wires to Sculcon as shown in the Wiring Diagram in Appendix
4.0. Use wire colors as indicated.  If other than suggested color codes are used, this information should be
so noted in the back of this manual for future reference and troubleshooting.

There is a factory installed jumper on TB2 terminals 1 and 2.  Remove the jumper if the control unit is to be
used with Scully’s SP-BLHK heated product sensor.  Otherwise, the jumper must be kept in place.

All wiring installation should be in accordance with local wiring codes.

Summary of Contents for ST-15C Series

Page 1: ...Model ST 15C Series Technical Manual Single Point Overfill Prevention Control Monitor scully ...

Page 2: ...ck Dynamic Self Checking Dynamic Faylsafe Go Anywhere Dynamic Self Testing IntelliCheck Intellitrol Scully Intelliview Load Anywhere Maxsafety R S V P Scully and V I P are registered trademarks of Scully Signal Company ...

Page 3: ...2 1 Mechanical Installation 9 2 2 Electrical Installation 9 2 2 1 Power Connections 10 2 2 2 Enclosure Earth Ground Connection 10 2 2 3 Control Output Controlled Circuit Connections 10 2 2 4 Intrinsically Safe Connections to Sculcon Plug Cable Unit 10 2 3 Initial System Checkout 11 2 3 1 Test Equipment 11 2 3 2 Operational Testing 11 3 0 MAINTENANCE 12 3 1 Enclosure 12 3 2 Corrosion Protection 12 ...

Page 4: ...n Box DWG 61442 18 Installation Wiring Diagram DWG 61575 19 Wiring Diagram Typical Loading Rack Control DWG 61441 20 Internal Wiring Diagram ST 15C EL DWG 31392 22 Internal Wiring Diagram ST 15C ELK DWG 31393 23 Replacement Parts List ST 15C 120VAC DWG 61558 Error Bookmark not defined Replacement Parts List ST 15C 240VAC DWG 61272 Error Bookmark not defined ...

Page 5: ...for immediate shutdown of the loading operation The ST 15C uses intrinsically safe voltage and current to connect to Scully liquid level sensors and provides control for external electrical devices by opening and closing relay contacts Scully loading rack overfill protection monitors have been carefully engineered to provide reliable and safe performance when installed in conjunction with related ...

Page 6: ... and the circuit is functioning properly Controller output is in permissive state i e permit to load OFF ON Sensor is wet or faulty or no connection to sensor or the circuit is malfunctioning Controller output is in non permissive state i e no permit to load OFF OFF No power to the unit 1 1 4 Bypass Control Switch Adding the suffix K to the model number adds a lockable two position control switch ...

Page 7: ...esponse Time PERMISSIVE Output goes permissive in 6 to 30 seconds typical of connection to a thermistor sensor warm up time of thermistor Output goes permissive instantaneously when connected to an optic sensor NON PERMISSIVE shutdown 0 5 second maximum Indicator Lights Output status indicator lights Red Non permissive Green Permissive Output Control Fuse Internal 5 Ampere Connections Provided by ...

Page 8: ...lug and cable assembly directly into the bottom of the ST 15C enclosure is not recommended and will result in greatly increased maintenance time and difficulty when the plug and cable assembly requires maintenance 1 3 1 Sculcon Junction Box with Plug and Cable Assembly The following model is needed to make connection to a vehicle The selection is based on the style of socket used on the vehicles B...

Page 9: ... holes provided for wiring The top two holes are for power and control wiring The bottom hole is for intrinsically safe sensor wiring only Do not drill any additional conduit holes in the enclosure doing so violates the enclosure s hazardous location approval and voids the warranty To avoid future maintenance issues regarding water infiltration into the enclosure via the electrical cable entries w...

Page 10: ...acket The output contact is rated 250VAC 5A resistive maximum It is used to close a valve or pump directly or by wiring it in series with other control contacts such as a preset meter s control contacts See Diagram 61441 Typical Loading Rack Control in Appendix 4 0 In addition it may also be connected to an input of a terminal automation system TAS to provide status of the controller s output to T...

Page 11: ...y sensors 2 wire thermistor or Optic Sensors As ST 15C is a single point controller monitors only one sensor the tester only needs to test in one of the eight positions of the selector switch on the tester Select switch position 5 to test the ST 15C As the tester simulates a vehicle equipped with 2 wire sensors the ST 15C output will go permissive immediately with green light ON and red light OFF ...

Page 12: ... Board The ST 15C control unit s internal circuitry does not require any routine periodic maintenance The control circuitry may be repaired only by replacing the internal control module with an equivalent module The internal module is non repairable DO NOT ATTEMPT TO SERVICE OR REPLACE COMPONENTS ON THE ST 15C MODULE DOING SO WILL NEGATE WARRANTIES CERTIFICATIONS AND JEOPARDIZE INTRINSIC SAFETY AS...

Page 13: ...tegrity must be maintained The ST 15C Control Module should not be subjected to any mechanical impact Do not allow build up of dust on the Control Module Caution Do not expose the Control Module to aggressive substances that may attack the exposed materials When used properly contact with the control module will not cause physical injury or harm and does not pose non electrical dangers The unit do...

Page 14: ... surface of the plug should be kept clean using a mild detergent based cleaning solution and water The cabling should be routinely wiped of foreign material and cleaned to preserve the outer jacket To protect it from loading arm damage etc it is important to store the plug and cable out of harms way when it is not in use A hook is provided on Sculcon Junction Box or a Scully Storage Socket may be ...

Page 15: ...15 ...

Page 16: ...16 4 0 APPENDIX Control Unit Enclosure Outline Drawing DWG 31412 ...

Page 17: ...17 Outline Drawing Sculcon Junction Box DWG 63039 ...

Page 18: ...18 Mounting Diagram Control Unit Junction Box DWG 61442 ...

Page 19: ...19 Installation Wiring Diagram DWG 61575 ...

Page 20: ...20 Wiring Diagram Typical Loading Rack Control DWG 61441 ...

Page 21: ...21 Notes ...

Page 22: ...22 Internal Wiring Diagram ST 15C EL DWG 31392 ...

Page 23: ...23 Internal Wiring Diagram ST 15C ELK DWG 31393 ...

Page 24: ...24 ...

Page 25: ...25 ...

Page 26: ...26 ...

Page 27: ...27 ...

Page 28: ...28 P N 61119 REV C ...

Reviews: