AnMNSP
Description:
Analog Input Minimum Setpoint.
The LOW setpoint for exception reporting.
Query
AT*AnMNSP
Query the MINIMUM (LOW) SETPOINT of the analog input.
Response value will be in either VOLTAGE or DECIMAL format, whichever one
is selected in the AUNITS register.
Options:
n = (1 – 8)
Response value is contingent upon the status of the AUNITS register.
(0.00 – 5.00) for units with 0-5VDC inputs when AUNITS=0
(0.00 – 30.00) for units with 0-30VDC inputs when AUNITS=0
(0.00 – 20.00) for units with 4-20mA inputs when AUNITS=0
(0 – 1023) when AUNITS=1
Configuration
AT*AnMNSP=y
Command to set the MINIMUM (LOW) SETPOINT for the analog input.
New value must be in the same format selected in the AUNITS register.
Options:
n = (1 – 8)
y = (0.00 – 5.00) for units with 0-5VDC inputs when AUNITS=0
y = (0.00 – 30.00) for units with 0-30VDC inputs when AUNITS=0
y = (4.00 – 20.00) for units with 4-20mA inputs when AUNITS=0
y = (0 – 1023) when AUNITS=1
AnMX
Description:
Analog Input Maximum
HIGHEST value attained since the last read request.
Query
AT*AnMX
Query the HIGHEST attained value for the analog input.
Response value will be in either VOLTAGE or DECIMAL format, whichever one
is selected in the AUNITS register.
Options:
n = (1 – 8)
Response value is contingent upon the status of the AUNITS register.
(0.00 – 5.00) for units with 0-5VDC inputs when AUNITS=0
(0.00 – 30.00) for units with 0-30VDC inputs when AUNITS=0
(0.00 – 20.00) for units with 4-20mA inputs when AUNITS=0
(0 – 1023) when AUNITS=1
Configuration
AT*AnMX=y
Command to reset the HIGHEST reached value for the analog input.
New value must be in the same format selected in the AUNITS register.
Options:
n = (1 – 8)
y = (0.00 – 5.00) for units with 0-5VDC inputs when AUNITS=0
y = (0.00 – 30.00) for units with 0-30VDC inputs when AUNITS=0
y = (4.00 – 20.00) for units with 4-20mA inputs when AUNITS=0
y = (0 – 1023) when AUNITS=1