FOR THE INSTALLER
Select the Location:
The unit can only be installed
indoors within the limitations
described on page 2.
The ice machine will have to be
connected to the buildings R-22
refrigeration system, check to be
sure that the system has enough
extra capacity to handle a
minimum of additional 16,000
BTU’s per hour @ 110
0
F. liquid
line temperature. Assume a 0
0
F.
evaporator temperature.
Storage Bin:
Scotsman’s B90 will be the
presumed bin of choice. If using
the bin extension, install heavy
duty leg kit KLP4 and place the
bin into position.
Remove the paper tape from the
bin edge gasket, and install the
bin extension onto the B90.
Remove the paper tape from the
bin extension top edge, and using
a mechanical lift, install the
NM1852RH onto the top of the
storage bin assembly.
Fasten the ice machine to the bin
using (4) 5/15-18 2.5" cap screws.
Level the assembly by:
a. Turning the leg levelers in or
out on the standard legs.
b. Use shims under the heavy
duty legs of the KLP4.
Locate the Nameplate: The
nameplate is located on the back
panel of the machine, and
contains the electrical characteristics
particular to the unit being installed.
Refrigeration Installation:
The skills of a refrigeration technician are
required to connect the ice machine to the
buildings refrigeration system.
//////////////////////////////Caution/////////////////////////////
Connect to a R-22 system only.
////////////////////////////////////////////////////////////////////////
Local Codes must be observed.
A P-trap should be installed where there will
be more than 10’ of vertical rise in the suction
line.
TYPICAL INSTALLATION: ALLOW ROOM FOR SERVICE ACCESS
NM1852RH
BIN
EXTENSION
B90 STORAGE
BIN
NM1852RH
August 1992
Page 3