FOR THE ELECTRICIAN
FAN RELAY KIT
To install the KCMR230 fan relay kit when
using (2) NM1250R icemakers and one 230
volt, two circuit remote condenser.
//////////////////////////////WARNING//////////////////////////
Do all wiring with electrical power OFF.
//////////////////////////////////////////////////////////////////////////
See the remote condenser nameplate for
current requirements to determine wire size to
be used for electrical hookup. Refer to wiring
diagram.
All external wiring should conform to the
national, state and local electrical codes.
Usually an electrical permit and services of a
licensed electrician will be required.
1. Mount the control box in a convenient
location.
2. Attach a solid earth ground wire to the
ground screw.
3. Route connecting wires from the first ice
maker junction box
(marked condenser fan) and connect it to the
KCMR230 terminal strip marked: NO. 1 ICE
MACHINE.
4. Route connecting wires from the second
machine junction box
(marked condenser fan) and connect it to the
KCMR230 terminal strip marked: NO. 2 ICE
MACHINE.
5. Route connecting wires from KCMR230
terminal strip marked: TO REMOTE FAN and
connect at the remote condenser junction box.
SUGGESTED
LOCATION
FOR KCMR230
CONTROL BOX
NM1250R
November, 1988
Page 11