FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES
Water Inlet
Connect the ice machine to cold
potable water. Use 3/8" O.D. copper
tubing, and connect to the 3/8" male
flare at the back of the cabinet. Install
a hand valve near the machine to
control the water supply.
Drains
There is one 3/4" FPT drain at the
back of the cabinet, the drain line is of
the gravity type, and 1/4 inch per foot
fall is an acceptable pitch for the drain
tubing. Install a vent at the highest
point of the drain line, and the ideal
drain receptacle would be a trapped
and vented floor drain.
Use only 3/4" rigid tubing.
Storage Bin:
Install a separate
gravity type drain. Insulation of this
drain line is recommended.
NME1854R & FME2404R
January 2000
Page 9
FLOOR DRAIN
VENT BIN DRAIN
3/4" FPT
VENT ICE
MACHINE
DRAIN,
3/4" FPT
WATER INLET
3/8" MALE
FLARE
FIELD SUPPLIED
WATER FILTER
HAND SHUT
OFF VALVE
CONNECT TO
COLD WATER