![SCM CUBO2 SMART Oem Manual Download Page 37](http://html1.mh-extra.com/html/scm/cubo2-smart/cubo2-smart_oem-manual_1217973037.webp)
OEM Manual – CUBO
2
SMART
Pag. 37
18
General information and limits
General Characteristics
Cubo2Smart line
UMTT 030 MT
UMTT 045 MT
UMTT 067 MT
UMTT 100 MT
models
Refrigerant
R744 (CO2)
Compressor
Toshiba
DY30N1F-10FU
DY45N1F-10FU
DY67L1F-10FU
RY100L1F-10FU
Motor
Rotary Compressor
Number of cylinders
1
1
2
2
Number of poles
4
Moto type
DC Brushless
Revolution range
25 ≈ 100 rps
25 ≈ 100 rps
25 ≈ 100 rps
25 ≈ 100 rps
Oil charged
520 ml
520 ml
450 ml
450 ml
Oil type
PAG VG100
Discharge working pressure
range
125 bar max
125 bar max
125 bar max
125 bar max
Suction working pressure range
12 ≈ 41 bar
12 ≈ 41 bar
12 ≈ 41 bar
12 ≈ 41 bar
Evaporating temperature
-15 °C ≈ +5 °C
Susction Superheating
10 K ≈ 20 K
Discharge temperature
max 130 °C
Ambient temp.
-15 °C ≈ +40 °C (Above 35 °C ambient, adiabatic option is required)
-20 °C only with winter kit option
System
EC fans (max)
In = 2,2A - P abs = 345W
Receveiver
2x 2,4 lt (2,4 lt Receiver max charge)
Suction line
3/8" K65 (9,52mm)
3/8" K65 (9,52mm)
3/8" K65 (9,52mm)
1/2" K65
(12,70mm)
Liquid line
3/8" K65 (9,52mm)
3/8" K65 (9,52mm)
3/8" K65 (9,52mm)
3/8" K65
(9,52mm)
PS Suction / Liquid
80 bar / 80 bar
PED Category
I
Dimensions (AxBxH)
1150 x 617 x 803 mm
Generic
Transport dimensions (AxBxH)
1300 x 700 x 950 mm
Gross weight
140 Kg
Transport way
Pallet & Carton
Painted
RAL 7035
Sound level (max speed)
1)
44 dBA
44 dBA
44 dBA
44 dBA
1)
Sound pressure and sound power analytically calculated. Sound pressure level at 10 m in free field.
19
Electrical details
Electrical Information
Cubo2 Smart line Size
UMTT 030 MT DX
UMTT 045 MT DX
UMTT 067 MT DX
UMTT 100 MT DX
Power Suply
230V/1Ph+N+PE/50Hz
400V/3Ph+N+PE/50Hz
Recommended protection
Circuit Breaker
Circuit Breaker
Circuit Breaker
Circuit Breaker
1+N C16A
1+N C20A
1+N C25A
3P C20A
MRA
11,6 A
16,1 A
23,1 A
17, 3 A
P abs max
2460 W
3500 W
5110 W
7900 W
MRA = Maximjum Rated Abs.
Unit is made in accordance with EN-60204-1. All electrical cabling, in external unit, have been
made in accordance with EN-60204-1.
All connection must be done by qualified persons according to legal standards in force in the
relevant countries and to EN-60204-1. Supply cable must be connected on terminal of upstream
main switch. Connect wire of ground (PE), from specific terminal block to system protection.