B.13
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
SEL-300 Series Relays Firmware Upgrade Instructions
Upgrade Procedure
G
.
Check Relay
Self-Tests
The relay can display various self-test fail status messages. The
troubleshooting procedures that follow depend upon the status message the
relay displays.
Step 1. Type
ACC <Enter>
.
Step 2. Type the Access Level 1 password and press
<Enter>
.
You will see the Access Level 1
=>
prompt.
Step 3. Enter the
STATUS
command (
STA <Enter>
) to view relay
status messages.
If the relay displays no fail status message, proceed to
Settings, Calibration, Status, Breaker Wear, and Metering on
page B.15
Table B.1
Troubleshooting New Firmware Upload
Problem
Solution
The restart was successful, but
the relay data transmission rate
reverted to the rate at which the
relay was operating prior to
entering SEL
BOOT
(the rate
).
Change the computer terminal speed to match the relay
data transmission rate you recorded in
. (See
Match Computer Communica-
tions Speed to the Relay on page B.9
):
Step 1. From the
Call
menu, choose
Disconnect
to
terminate relay communication.
Step 2. Change the communications software settings
to the values you recorded in
.
Step 3. From the
Call
menu, choose
Connect
to rees-
tablish communication.
Step 4. Press
<Enter>
to check for the Access
Level 0
=
prompt indicating that serial com-
munication is successful.
Step 5. If you get no response, proceed to
Match
Computer Communications Speed to the
Relay on page B.9
.
The restart was successful, but
the relay data transmission rate
reverted to 2400 bps (the set-
tings have been reset to
default).
Match the computer terminal speed to a relay data
transmission rate of 2400 bps:
Step 1. From the
Call
menu, choose
Disconnect
to
terminate relay communication.
Step 2. Change the communications software settings
to 2400 bps, 8 data bits, no parity, and 1 stop
bit (See
Match Computer Communications
Speed to the Relay on page B.9
).
Step 3. From the
Call
menu, choose
Connect
to rees-
tablish communication.
Step 4. Press
<Enter>
to check for the Access
Level 0
=
prompt indicating successful serial
communication.
If you see a SEL
boot !>
prompt, type
EXI <Enter>
to exit SEL
BOOT
. Check for
the Access Level 0
=
prompt.
If you see the Access Level 0
=
prompt, pro-
ceed to
The restart was unsuccessful,
in which case the relay is in
SEL
BOOT
.
Reattempt to upload the new firmware (beginning at
Step 5
under
Establish a High-Speed Connection on
page B.8
) or contact the factory for assistance.
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...